35kV降压变电站电气主接线设计

更新时间:2023-10-29 18:21:52 阅读: 评论:0

我们都哭了-中小学管理

35kV降压变电站电气主接线设计
2023年10月29日发(作者:h影视)

( )

电气工程及其自动化

系(院) 专业

课程设计(论文)题目 35kV

降压变电站电气主接线设计

学生姓名

指导教师

完成日期

2012 12 12

评语:

指导教师:

成绩:

- 2 -

35KV降压变电站电气主接线设计

The 35KV the buck substation electrical main wiring design

总计 课程设计(论文) 18

··································································- 1

-

前言

······································································ 1

第一章 主接线的选择

····················································· 4

1.1变电站主接线选择的基本要求············································4

1.2主接线的方案的拟定···········································5

1.3主接线的比较与选定····················································7

第二章短路电流的计算

···················································10

2.2短路计算的目的······················································· 10

2.2短路电流的计算步骤及结果············································· 10

2.3无功补偿计算校验····················································· 15

第三章主要电气设备的选择

··············································16

3.135KV断路器和隔离开关的选择·········································16

KV

3.235互感器的选择·····················································17

KVK

3.310母线及35V线路的选择···········································19

3.410KV开关柜选择·······················································19

第四章车间变压器的选择

················································21

4.1所用变的选择··························································21

4.2.1所用变台数的选择···················································21

4.2.2所用变容量的选择···················································22

南昌工程学院

变电站,改变电压的场所。为了把发电厂发出来的电能输送到较远的地方,必须把

电压升高,变为高压电,到用户附近再按需要把电压降低,这种升降电压的工作靠变电站

来完成。变电站的主要设备是开关和变压器。按规模大小不同,称为变电所、配电室等。

对于35KV降压变电站,要根据运行可靠、灵活、且经济的原则进行比较,首先应选取

可靠性高且经济性好的最优的电气主接线方式;其次选择本变电站主变的台数、容量和型

号。根据所选的变压器进行短路电流计算校验,由各短路电流算出短路稳态电流和短路冲

击电流,对主要设备选择及校验,其中包括断路器、隔离开关、电压互感器、电流互感器

等;最后根据各电压等级的额定电压和最大长期工作电流进行电气设备的选择。

线

- 2 -

南昌工程学院

前言

本次课程设计为35KV降压变电站电气主接线设计,原始资料及设计技术要求如下:

1. 全厂用电设备情况

1)负载大小

用电设备总安装容量:6630kW

计算负荷(10KV侧)有功:4522kW

无功:1405kVAR

各车间负荷统计见表1

1 全厂各车间负荷统计表

负荷

类型

车间名称

780 180 800 1 空气压缩车间

560 150 580 2 熔制成型(模具)车间

590 170 614 3 熔制成型(熔制)车间

650 220 686 4 后加工(磨抛)车间

560 150 580 5 后加工(封接)车间

360 100 374 6 配料车间

420 110 434 7 锅炉房

Ⅱ~Ⅲ 400 168 434 8 厂区其他负荷(一)

Ⅱ~Ⅲ 440 200 483 9 厂区其他负荷(二)

4760 1448 共计

PkW Q(kVAR) SkVA

jsjsjs

0.95 0.97 同时系数

4522 1405 4735.24

全厂计算负荷

- 2 -

南昌工程学院

2)负荷类型

本厂绝大部分用电设备均属于长期连续负荷,要求不间断供电。停电时间超过两分钟

将造成产品报废;停电时间超过半小时,主要设备池,炉将会损坏;全厂停电将造成严重

经济损失,故主要车间及辅助设施均为Ⅰ类负荷。

3)本厂为三班工作制,全年工作时数8760小时,最大负荷利用小时数5600小时。

4)全厂负荷分布:见厂区平面示意图(图1

8

5 3

4 2

7

9

电源

1

6

1 厂区平面示意图

2. 电源情况

1)工作电源

本厂拟由距其5公里处A变电站接一回架空线路供电,A变电站110kV母线短路容量

1918MVA,基准容量为1000MVA A变电站安装两台SFSLZ31500 kVA/110kV三卷变

1

压器,其短路电压u=10.5%u=17%u=6%,详见电力系统与本厂联接示意图

(图2

供电电压等级:由用户选用35KV10KV的一种电压供电。

最大运行方式:按A变电站两台变压器并列运行考虑。

最小运行方式:按A变电站两台变压器分列运行考虑。

2)备用电源

拟由B变电站接一回架空线路作为备用电源。系统要求,只有在工作电源停电时才允

许备用电源供电。

- 3 -

高—中高—低低—中

南昌工程学院

3)功率因数

供电部门对本厂功率因数要求值为:

35KV供电时,cosφ=0.9

10KV供电时,cosφ=0.95

4)电价

供电局实行两部电价

基本电价:按变压器安装容量每1千伏安每月10元计费。

电度电价:35KV β=0.40/kwh

10KV β=0.41/kwh

南昌工程学院

课程设计任务及设计大纲

1.高压供电系统的设计

根据供电部门提供的资料,选择本厂最优供电电压等级。

2.总压降变电站设计

1)主接线设计:根据设计任务书,分析原始资料与数据,列出技术可能实现的多个方

案,经概略分析比较,留下2~3个较优方案,对较优方案进行详细计算和分析比较,确定

最优方案。

2)短路电流计算:根据电气设备选择和继电保护的需要,确定短路计算点,计算短路

电流,计算结果列出汇总表。

3)主要电气设备选择:主要电气设备的选择,包括断路器、隔离开关、互感器、导线型

号的选择和校验。选用的设备型号、数量汇成设备一览表。

3.车间变电所设计

根据负荷情况,选择车间变压器的台数、容量以及变电所的位置的原则考虑。

4.厂区10kv配电系统设计

根据所给资料,列出配电系统结线方案,经过详细计算和分析比较,确定最优方案。

南昌工程学院

第一章 电气主接线的选择

一、变电站主接线基本要求

1、运行的可靠性

断路器检修时是否影响供电;设备和线路故障检修时,停电数目的多少和停电时间的长短,以及能

否保证对重要用户的供电。安全可靠是电力生产的首要任务,保证供电可靠是电气主接线最基本的要求。

因此主接线的接线形式必须保证供电可靠。

2、具有一定的灵活性

主接线正常运行时可以根据调度的要求灵活的改变运行方式,达到调度的目的,而且在各种事故或

设备检修时,能尽快地退出设备。切除故障停电时间最短、影响范围最小,并且再检修在检修时可以保

证检修人员的安全。

3、操作应尽可能简单、方便

主接线应简单清晰、操作方便,尽可能使操作步骤简单,便于运行人员掌握。复杂的接线不仅不便

于操作,还往往会造成运行人员的误操作而发生事故。但接线过于简单,可能又不能满足运行方式的需

要,而且也会给运行造成不便或造成不必要的停电。

4、经济上的合理性

主接线在保证安全可靠、操作灵活方便的基础上,还应使投资和年运行费用小,占地面积最少,使

其尽地发挥经济效益。

5、应具有扩建的可能性

由于我国工农业的高速发展,电力负荷增加很快。因此,在选择主接线时还要考虑到具有扩建的可

能性。

变电站电气主接线的选择,主要决定于变电站在电力系统中的地位、环境、负荷的性质、出线数目

的多少、电网的结构等。

- 6 -

南昌工程学院

二、厂最优供电电压等级的选择

根据所给资料可知,本所电源分为35kV10kV的两种,则可供选择的供电方案有三

种,分别为:

方案一:工作35kV,备用35kV

方案二:工作10kV,备用10kV

方案三:工作35kV,备用10kV

三个方案的主接线图

1-1 两路都是35KV的供电方案(方案一)

- 7 -

南昌工程学院

1-2 两路都是10KV的供电方案(方案二)

1-3 工作电源采用35KV 备用电源采用10KV的供电方案(方案三)

- 8 -

南昌工程学院

按照要求正常情况下两路电源一路供运行,另一路作为备用,厂内配电母线为10kV

根据负荷情况出线有5条,且对供电可靠性要求较高,因此考虑配电母线采用单母分段接

线,为了提高供电可靠性,10kV拟采用成套开关柜布置。

现对各方案进行分析比较

1)方案一 工作电源和备用电源均采取35kv供电。优点:供电时电压高,线路功率损耗少,要求的

功率因数值低,所需补偿容量少,供电可靠性高。缺点:总降压变电所装设两台主变压器,投资及运行

维护费用高,备用35kV正常情况下不工作,使得能源利用率较低,不够经济。

2)方案二 工作电源和备用电源均采用10kv供电。优点:工厂内不设主变压器,可以简化线路,降

低了投资及运行维护费,可以减少占地面积,减少管理人员及维护的工作量。缺点:供电电压低,线路

的功率损耗增大,电压损失也大,要求的功率因数值高,还需增加补偿装置及相关的投资,工厂内设总

配电所供电的安全可靠性不如35kv

3方案三 工作电源采用35kv供电,备用电源采用10kv供电。本方案的技术经济指标介于方案一和

方案三之间,但是由于原始资料要求两路电源正常时只用一路供电,工作电源停运时才使用备用电源进

行供电,因此该方案适合。因为备用电源供电时间较少,所以该方案既能满足供电可靠性要求,投资也

相对较少。

- 9 -

南昌工程学院

根据所给资料及要求进行分析,决定该变电所进行主接线设计方案采用方案三。

如下图

1-3 工作电源采用35KV 备用电源采用10KV的供电方案(方案三)

- 10 -

南昌工程学院

第二章 短路电流计算

一、

计算短路电流的目的

计算短路电流的目的是为了限制短路的危害和缩小故障的影响范围。在变电所和供电系统

的设计和运行中,基于如下用途必须进行短路电流的计算:

⑴选择电气设备和载流导体,必须用短路电流校验其热稳定性和动稳定性。

⑵选择和整定继电保护装置,使之能正确的切除短路故障。

⑶确定合理的主接线方案、运行方式及限流措施。

⑷保护电力系统的电气设备在最严重的短路状态下不损坏,尽量减少因短路故障产生的危

害。

二、短路电流计算步骤

1.确定计算条件,画计算电路图

1)计算条件:系统运行方式,短路地点、短路类型和短路后采取的措施。

2)运行方式:

根据计算目的确定系统运行方式,画相应的计算电路图。

选电气设备:选择正常运行方式画计算图;

短路点取使被选择设备通过的短路电流最大的点。

2.画等值电路,计算参数;

分别画各段路点对应的等值电路。

- 11 -

南昌工程学院

等值电路图

2-2 短路等值电路图

2-3 最大运行方式等值电路图

- 12 -

南昌工程学院

2-4 最小运行方式等值电路图

此次35kV侧主变压器选用SZ9-5000/35型有载调压变压器

据网上资料得知SZ95000/35型有载调压变压器,额定容量为5000kVA,电压为35kV,主

要技术数据:

空载损耗为5.8kw,短路损耗36kw,空载电流I%=1.2,阻抗电压

U%7

K

由所给资料可得

电力系统的电抗标幺值

X1.92

d

S

d

1918MVA

S1000MVA

B

11

U-%+U-%-U-% ==10.75

(10.5176)Us2%

2

2

11

Us3%(10.5617)

U-%+U-%-U-%=-0.25

2

2

线路L

X1.6

l

x*l*S21000

B

Un*Un3535

主变压器:

X3.41

2

U%S

kB

10.751000

100S10031.5

N

- 13 -

南昌工程学院

X0.08

3

U%S

kB

0.251000

100S10031.5

N

U%S

kB

71000

14X

100S1005

N

1

最大运行方式下

K1点短路电流:

总电抗标幺值:X*=1.92+(3.41-0.08)/2+1.6=5.18

I15.3kA

B

S1000

B

3U337

av

II/x*15.3/5.182.95kA

K1B

三相短路次暂态电流和稳态电流

(3)''(3)

III2.95kA

K1

三相短路冲击电流:查电力系统分析P160=1.8

K

sm

(3)''(3)

i2KI21.82.957.5kA

shsm

(3)

三相短路容量:

S.1MVAS/x*1000/5.18193

K1d

K2点短路电流:

总电抗标幺值:

x'5.181419.18

*

I54.1kA

B

S1000

B

3U310.5

av

II/x'*54.1/19.182.8kA

K2d2

三相短路次暂态电流和稳态电流:

(3)''(3)

III2.8kA

K2

- 14 -

南昌工程学院

三相短路冲击电流:查电力系统分析P160=1.8

K

sm

(3)''(3)

i2KI21.82.87.13kA

shsm

三相短路容量:

(3)

SS/x'*1000/19.1852.14MVA

K1d

2-1 最大运行方式下,三相短路,各点计算值

短路点计算点

k1 193.1 2.95 2.95 2.95 7.5

k2 52.14 2.8 2.8 2.8 7.13

三、系统无功补偿校验

1.无功补偿的原理

电网输出的功率包括两部分;一是有功功率;二是无功功率.直接消耗电能,把电能转

变为机械能,热能,化学能或声能,利用这些能作功,这部分功率称为有功功率;不消耗电能;

只是把电能转换为另一种形式的能,这种能作为电气设备能够作功的必备条件,并且,这种

能是在电网中与电能进行周期性转换,这部分功率称为无功功率,如电磁元件建立磁场占

用的电能,电容器建立电场所占的电能.电流在电感元件中作功时,电流超前于电压90℃.

而电流在电容元件中作功时,电流滞后电压90℃.在同一电路中,电感电流与电容电流方向

相反,互差180℃.如果在电磁元件电路中有比例地安装电容元件,使两者的电流相互抵消,

使电流的矢量与电压矢量之间的夹角缩小,从而提高电能作功的能力,这就是无功补偿的

道理.

2.无功补偿的意义

(1)补偿无功功率,可以增加电网中有功功率的比例常数

- 15 -

Ii

ksh

(3)3

kA (kA)

I

''(3)

(kA)

(3)

I

(kA)

南昌工程学院

(2)减少发,供电设备的设计容量,减少投资

(3)降低线损

所以提高功率因数后,线损率也下降了.减少设计容量,减少投资,增加电网中有功功

率的输送比例,以及降低线损都直接决定和影响着供电企业的经济效益.所以,功率因数是

考核经济效益的重要指标,规划、实施无功补偿势在必行.

整个厂区无功功率补偿计算:

由前言可得该厂区计算负荷P=4522kWQ=1405kVA

cos0.9549670.9

P4522

22

S

45221405

由公式计算可知,该系统无需进行无功补偿。

- 16 -

南昌工程学院

第三章 电气设备的选择

一、35KV断路器和隔离开关的选择

高压断路器主要功能是:正常运行时用来切换线路运行方式,把设备或线路投入运行

或退出运行,起控制作用;当设备或线路发生故障时,因为有灭弧作用,能快速切除故障

回路,保证无故障部分正常运行,起保护作用。高压短路器最大特点是能断开电气设备中

负荷电流和短路电流。而隔离开关的主要功能是保证高压电气设备及装置在检修工作时的

安全,形成明显的电气隔离,但不能用于切断或投入负荷电流或开断短路电流,仅可允许

用于开断小电流。

高压断路器的额定电压和电流选择需满足

UU,II

NSNNmax

式中:分别为断路器和电网的额定电压(KV分别为断路器的额

UUII

NSNNmax

定电流和电网的最大负荷电流(A

I86.6A

max

1.05S

N

1.055000

3U335

N

U35kV

SN

IU

maxN

及安装在屋外的要求,根据35K断路器和隔离开关的查表,可选择LW35/630

- 17 -

南昌工程学院

型断路器,固有分闸时间和燃弧时间均为0.065s主保护时间1.5s后备保护时间0.065s

根据上面计算出的短路电流值为:

II2.95kAI2KI7.5kA

kshimk

"

tttt1.65s

kprina

22''2

I10II

tk/2tk

14.36(kAs)Qt

2

短路电流周期分量的热效应:

Kk

12

由于设计手册规定:远离发电厂的变电站和配电网无需考虑非周期分量的影响,故不

计非周期热应。因此短路电流引起的热效应:

Q14.36[(KA)S]

k

2

3-1 LW35/630型断路器和GW235G型隔离开关的相关参数与计算的数据

计算数据 LW35/630型断路器 GW235G型隔离开关

UUU

SNNN

III

naxNN

II

NbrNbr

iii

NclNclsh

ItIt

tt

22

35KV 35/40.5KV 35KV

86.6A 630A 600A

2.95KA 25KA

7.5KA 63KA

I

''

Q

k

14.36[(KA)S]

2

251.63204

22

1018.75[(KA)S]1600[(KA)S]

22

iii

eseses

7.5KA 63KA 42KA

二、35kv互感器的选择

- 18 -

南昌工程学院

1、按额定电流的选择:

I1.051.051.0582.4886.6A

max

S

N

3U335

N

5000

(3)

''(3)(3)

i7.5KA

II

II2.95KA

Nmax

sh

2、按额定电压选择: =35kV

UU

NNS

上网查资料获得 LCWD-35 10P/0.5电流互感器的技术参数

定电额定二次负荷 10%1s动稳

流比A 等级 倍数

kA kA

0.8

35 90 150

型号

LCWD-35 600/5 10p

10P/0.5

因各参数符合要求,则选择LCWD-35 10P/0.5型电流互感器

3、热稳定校验:

热稳定满足条件

(KI)(902.95)70490.25(kA)S

tN

222

4、动稳定校验:

动稳定满足要求 所选的电流互感器合

2KI22.95150625.7kA7.5kA

esN

5、电压互感器的选择

型号

- 19 -

额定工作电压V

南昌工程学院

JDZXW2-35

压互感器主要技术数据

一次线圈 二次线圈 辅助线圈

100/

3

JDZXW2-35 35000/ 100/

33

三、10kv母线及35kV线路的选择

I1.05I1.05S/(3U)1.055000/(310)303.1A

max

nNN

I1.05I1.05S/(3U)1.055000/(335)86.6A

maxlnNN

线路:采用LGJ-95的钢芯铝绞线架设,其电抗率,载流量335A

x0.40/km

0

求得线路35kV线路最大电流为86.6A,则满足要求。

查《工厂供电》苏文成编著,附录表11P380,母线选用 40*4mm矩形铝导体,允许

电流为480A ,允许电流为395A S=160满足最大持续工作电流的要求。

mm

2

四、10KV开关柜选择

I303.1Ai7.5KA

maxsh

I2.95KA

''

计算数据与VD4断路器技术数据对比

计算数据 VD4断路器

Un 10KV 10KV

U

N

- 20 -

南昌工程学院

II

naxN

303.1 A 630A

2.95KA 16KA

7.5KA 40KA

I

Nbr

ii

Nclsh

I

''

GZS112开关柜技术数据

回路名称 受电、馈电 隔离+联络(左) 所用变

联络电压测量+

(右) 避雷器

011 041方案号 004 055 078

630A 630A额定电流 630A 630A 630A

1 断路器VD4 1

电流互感器

AS12-150B/43 3

S

电压互感器

RZL-10

熔断器

RNZ-10

避雷器 3

3 2

3

- 21 -

南昌工程学院

第四章 车间变电所设计

变压器容量选择时应遵循的原则

1、只装有一台变压器的变电所,变压器的额定容量应满足全部用电设备计算负荷的需要。

2、装有两台变压器的变电所,每台变压器的额定容量应同时满足以下两个条件:

1、任一台变压器单独运行时,应满足全部一、二级负荷的需要;

2、任一台变压器单独运行时,宜满足全部用电容量设备的需要。

3、变压器正常运行时的负荷率应控制在额定容量的为宜,以提高运行率。各

70%~80%

车间变压器台数及容量选择和无功补偿。

南昌工程学院

2号熔制成型(模具)车间、3号熔制成型(熔制)车间)配变压器一台

4号后加工(磨抛)车间、5号后加工(封接)车间)配变压器一台

6号配料车间、8号厂区其他负荷(一))配变压器一台

7号锅炉房、9号厂区其他负荷(二))配变压器一台

配电房a1号空气压缩车间)变压器选择,由统计表可得该计算负荷为800KVA,为保证

供电的可靠性,选用变压器SCB10-800/10,额定容量为800KVA

配电房b2号和3号车间)变压器选择,由统计表可得该负荷的计算负荷为1194KVA,为

保证供电的可靠性,选用变压器SCB10-1250/10,额定容量为1250KVA

配电房c4号和5号车间)变压器选择,由统计表可得该负荷的计算负荷为1266KVA,为

保证供电的可靠性,选用变压器SCB10-1250/10,额定容量为1250KVA

配电房d6号和8号车间)变压器选择,由统计表可得该负荷的计算负荷为808KVA,为

保证供电的可靠性,选用变压器SCB10-800/10,额定容量为800KVA

配电房e7号和9号车间)变压器选择,由统计表可得该负荷的计算负荷为917KVA,为

保证供电的可靠性,选用变压器SCB10-1000/10,额定容量为1000KVA

4-1 SCB10系列各型号的参数

型号 额定电压(kV 损耗(W 阻抗空载电流(%

- 23 -

南昌工程学院

容量电压

高压 空载 负载

% kVA

SCB10-800/10 800 1520 6960 6 1.0

Y

yn0

Y

yn0

Y

yn0

SCB10-1000/10 1000 10.5 0.4 1770 8130 6 1.0

SCB10-1250/10 1250 2090 8690 6 1.0

参考文献

[1]刘介才. 《工厂供电设计指导》[M]. 北京: 机械工业出版社, 1999.

[2]苏文成. 《工厂供电》[M]. 2. 北京: 机械工业出版社, 1999.

[3]熊信银, 朱永利. 《发电厂电气部分》[M]. 4. 北京: 中国电力出版社, 2009

[4]孟祥萍, 高嬿. 《电力系统分析》[M]. 北京: 高等教育出版社, 2004

[5]王子午,徐泽植. 《常用供配电设备选型手册》 第三分册[M]:高压电器. 北京.

炭工业出版社. 1997

[6]王子午,徐泽植. 《常用供配电设备选型手册》 第五分册[M]:组合(箱式)变电站、

变压器及附录. 北京. 煤炭工业出版社. 1997

[7]刘学军. 《继电保护原理》[M]. 2. 北京. 中国电力出版社. 2007

- 24 -

电子信箱格式-小王子阅读感想

35kV降压变电站电气主接线设计

本文发布于:2023-10-29 18:21:51,感谢您对本站的认可!

本文链接:https://www.wtabcd.cn/zhishi/a/1698574912200281.html

版权声明:本站内容均来自互联网,仅供演示用,请勿用于商业和其他非法用途。如果侵犯了您的权益请与我们联系,我们将在24小时内删除。

本文word下载地址:35kV降压变电站电气主接线设计.doc

本文 PDF 下载地址:35kV降压变电站电气主接线设计.pdf

留言与评论(共有 0 条评论)
   
验证码:
推荐文章
排行榜
Copyright ©2019-2022 Comsenz Inc.Powered by © 实用文体写作网旗下知识大全大全栏目是一个全百科类宝库! 优秀范文|法律文书|专利查询|