AMCA Standards 99-2404-03, 99-2410-03 (e pages 2,3 and 7). The pages illustrate the usual fan arrangements with their proper numbers. When ordering fans, or when requesting data or prices, the required fan arrangement MUST always be indicated.
Inlet Box Positions For Centrifugal Fans
Standard 99-2405-03 (e page 4 and 8). This page shows proper designations for inlet box positions, in degrees. When ordering fans with inlet boxes this information is required.
十大幼儿英语品牌Designations For Rotation & Discharge Of Centrifugal Fans
AMCA Standard 99-2406-03 (e page 5). Proper terminology is clearly indicated on this page. When ordering equipment, or when requesting certified prints,always be sure to include this information. No order will begin fabrication without it, if in doubt as to proper designation, draw a sketch. In the event that an angular discharge is required that is NOT at 45º, be sure to clearly state what is required, such as “top angular down 30º from horizontal” or “bottom angular up 20º from horizontal.” Here again, draw a sketch if in doubt.
Motor Positions For Belt Drive Centrifugal Fans
AMCA Standard 99-2407-03 (e page 6). This page indicates standard nomenclature for properly locating the motor in reference to the drive side of the fan. It is fully accepted by the industry and vibration ba manufacturers as well. If a bare fan without motor or drive is ordered this information is not needed; but whenever a drive or vibration ba is to be included this information is absolutely necessary. Plea note that motor position is always determined from the drive side of the fan, and has no reference whatsoever to fan rotation or discharge.
harbin weather>exunPrinted in the USA Jan 2005
ED 16002
Data contained in this issue should be thoroughly understood, as it is important in properly choosing, applying, pricing and ordering centrifugal and axial fans of all types. The terminology contained is a standard with the Air Movement and Control Association (AMCA) and has been adapted by the industry as a whole. It should be a part of your everyday language when considering fans.
Engineering Data 16002AMCA Standards On Fan Arrangements, Rotation, Discharge & Motor Position
美国留学新政策
2PENNBARRY
1401 North Plano Road, Richardson, Texas 75081Phone: 972-234-3202Fax: 972-497-0468
Drive Arrangements For Centrifugal Fans AMCA Standard 99-2404-03
汽车天窗NOTES:
SW - Single Width DW - Double Width SI - Single Inlet
DI - Double Inlet
Arrangements 1, 3, 7 and 8 are also available with bearings
mounted on pedestals or ba t independent of the fan housing.For designation of rotation and discharge, e page 5.For motor position, belt or chain drive, e page 6.
For designation of position of inlet boxes, e page 4.
ARR. 1 SWSI - For belt drive or direct connection. Impeller
用英文打电话ARR. 3 DWDI - For belt drive or direct connection. One bearing on each side and supported by fan housing.
ARR. 7 DWDI - For belt drive or direct connection. Arrangement 3plus ba for prime mover.
ARR. 10 SWSI - For belt drive.Impeller overhung, two bearings,with prime mover inside ba.
ARR. 3 SWSI - For belt drive or direct connection. One bearing on each side and supported by fan h
ousing.
ARR. 7 SWSI - For belt drive or direct connection. Arrangement 3plus ba for prime mover.ARR. 9 SWSI - For belt drive.Impeller overhung, two bearings,with prime mover outside ba.direct connection. Impeller overhung. Bearings in bracket supported by fan housing.ARR. 4 SWSI - For direct drive.Impeller overhung on prime mover shaft. No bearings on fan. Prime mover ba mounted or integrally directly connected.
ARR. 8 SWSI - For belt drive or direct connection. Arrangement 1 plus
extended ba for prime mover.
Engineering Data 16002
AMCA Standards On Fan Arrangements, Rotation, Discharge & Motor Position PENNBARRY 3
1401 North Plano Road, Richardson, Texas 75081Phone: 972-234-3202
Fax: 972-497-0468
Drive Arrangements For Centrifugal Fans AMCA Standard 99-2404-03
NOTES:
SW - Single Width DW - Double Width SI - Single Inlet
DI - Double Inlet
For designation of rotation and discharge, e page 5.For motor position, belt or chain drive, e page 6.For designation of position of inlet boxes, e page 4.
ARR. 1 SWSI With Inlet Box - For belt drive or direct connection. Impeller overhung, two bearings on ba. Inlet box may be lf-supporting.
ARR. 3 SWSI With Inlet Box and Independent Pedestals - For belt drive or direct connection fan.Housing is lf-supporting. One bearing on each side supported by independent pedestals with shaft
extending through inlet box.
ARR. 3 SWSI With Independent Pedestal - For belt drive or direct connection fan. Housing is lf-supporting. One bearing on each side
supported by independent pedestals.
ARR. 3 DWDI With Independent Pedestal - For belt drive or direct connection fan. Housing is lf-supporting. One bearing on each side
supported by independent pedestals.
ARR. 8 SWSI With Inlet Box - For belt drive or direct connection.Impeller overhung, two bearings on ba plus extended ba for prime mover. Inlet box may be lf-supporting.
ARR. 3 DWDI With Inlet Box and Independent Pedestals - For belt drive or direct connection fan.Housing is lf-supporting. One bearing on each side supported by independent pedestals with shaft
extending through inlet box.
Inlet Box PositionsFor Centrifugal Fans
AMCA Standard 99-2405-83
NOTES:
1.Reference line is the top vertical axis through center of fan shaft.
flash player是什么2.Position of inlet box and air entry to inlet box in determined from DRIVE SIDE OF FAN.
3.Position on inlet box is designated in degrees clockwi from top vertical axis as shown,
and may be any intermediate angle as required.
4.Positions 135° to 225° in some cas interfere with floor structure.
Engineering Data 16002AMCA Standards On Fan Arrangements, Rotation, Discharge & Motor Position
dido
4PENNBARRY 1401 North Plano Road, Richardson, Texas 75081 Phone: 972-234-3202Fax: 972-497-0468
高升专报考条件Designations For Rotation & Discharge Of Centrifugal Fans AMCA Standard 99-2406-03
Engineering Data 16002
AMCA Standards On Fan Arrangements, Rotation, Discharge & Motor Position PENNBARRY 5
1401 North Plano Road, Richardson, Texas 75081Phone: 972-234-3202Fax: 972-497-0468
NOTES:
1.Direction of rotation is determined from drive side of fan (e Note 2 and 3).
2.On single inlet fans, drive side is always considered as the side opposite fan inlet (even when driven through fan inlet).
3.On double inlet fans with drives on both sides, drive side is that with the higher powered drive unit.
4.Direction of discharge is determined in accordance with diagrams. Angle of discharge is referred to the vertical axis of fan
and designated in degrees from such standard reference axis. Angle of discharge may be any interm
ediate angle as required.5.For fan inverted for ceiling suspension, or side wall mounting, direction of rotation
and discharge is determined when fan is resting on floor.
Down Blast CW 180Bottom Angular Down
CW225Bottom Horizontal
CW270Bottom Angular Up
CW315
Engineering Data 16002AMCA Standards On Fan Arrangements, Rotation, Discharge & Motor Position
6PENNBARRY 1401 North Plano Road, Richardson, Texas 75081 Phone: 972-234-3202Fax: 972-497-0468
Motor Positions For Belt Or Chain Drive Centrifugal Fans
AMCA Standard 99-2407-03
NOTE:
Location of motor is determined by facing the drive side of fan and designating the motor positions by letters W, X, Y or Z as
the ca may be.