General Note
AEI Cables rerves the right to amend the product information without notice or liability.
The information is considered accurate at the time of going to print.
© AEI Cables Limited Durham Road, Birtley, Chester-le-Street, County Durham DH3 2RA
Constructional and Electrical Performance Data
BS5467/BS6724 – 0.6/1.0kV – Single core
Aluminium
conductors
thermotting
insulated
armoured
哈密瓜的英文cables AEI Cables Limited
Nominal area of conductor mm² 50.00* 70.00* 95.00* 120.00* 150.00* 185.00* 240.00* 300.00* 380.00! 480.00! 600.00! 740.00! 960.00! 1200.0!
Insulation
radial
thickness mm 1.00 1.10 1.10 1.20 1.40 1.60 1.70 1.80 2.00 2.20 2.40 2.60 2.80 3.00
Inner
sheath
radial
thickness mm 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.20 1.20 1.20 1.40 1.40 1.60
Aluminium
armour
wire
diameter mm 1.25 1.25 1.25 1.25 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.50 2.50 2.50
Outer
sheath
radial
thickness mm 1.50 1.50 1.60 1.60 1.70 1.80 1.80 1.90 2.00 2.10 2.20 2.30 2.50 2.60
Overall
diameter
(Nom) mm 17.00 19.00 21.00 23.00 26.00 28.00 30.00 33.00 38.00 41.00 45.00 50.00 53.00 61.00
4级准考证Cable
weight
(Nom) Kg/Km 400 550 650 750 950 1150 1350 1650 2150 2550 3000 3800 4700 5700
Internal
bending
radius
(Min) mm 136 152 168 184 208 224 240 264 304 328 360 400 424 488
Armour resistance @ 20°C (Max) Ω/Km 1.40 0.84 0.75 0.69 0.47 0.42 0.38 0.35 0.25 0.22 0.20 0.15 0.13 0.12
Armour
gross
cross
ctional
area mm² 24 38 42 46 68 76 84 95 131 147 160 225 250 279
Armour
conductivity % 46 53 43 37 44 39 33 29 32 29 26 27 24 21
< conductor resistance @ 20°C (Max) Ω/Km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0800 0.0633 0.0515 0.0410 0.0313 0.0250
< conductor resistance @ 90°C (Max) Ω/Km 0.822 0.555 0.411 0.325 0.265 0.211 0.162 0.130 0.125 0.0837 0.0692 0.0565 0.0451 0.0381
Inductance mH/Km 0.344 0.339 0.327 0.312 0.315 0.308 0.302 0.291 0.296 0.293 0.286 0.285 0.280 0.275
Reactance @ 50 Hz Ω/Km 0.108 0.106 0.103 0.098 0.099 0.097 0.095 0.091 0.093 0.092 0.090 0.090 0.088 0.086
Impedance @ 90°C Ω/Km 0.829 0.565 0.424 0.339 0.283 0.232 0.188 0.159 0.140 0.124 0.113 0.106 0.0989 0.0944
DC
voltage
drop mV/A/M 1.60 1.10 0.82 0.66 0.52 0.42 0.32 0.26 0.21 0.160 0.130 0.105 0.080 0.064
Single
pha
voltage
drop mV/A/M 1.60 1.15 0.85 0.69 0.57 0.47 0.39 0.33 0.29 0.25 0.24 0.22 0.20 0.19
Three
pha
voltage
drop mV/A/M 1.40 0.98 0.74 0.60 0.49 0.41 0.34 0.29 0.25 0.22 0.20 0.19 0.175 0.165
Continuous
current
carrying
capacity
(Laid
direct) A 177 218 260 296 331 374 433 486 546 611 672 734 810 874
Continuous
current
carrying
sand
capacity
(Ducts) A 178 216 255 288 315 350 397 438 474 517 557 591 642 688
Continuous
current
carrying
capacity
(Air) A 173 221 271 314 362 417 494 566 655 748 839 940 1063 1172
Conductor
short
circuit
symmetrical
fault
90°C
–
250°C
for
1
c kA
rms 4.70 6.60 8.90 11.30 14.10 17.40 22.60 28.20 35.70 45.10 56.40 69.60 90.20 >100
Armour
short
circuit
asymmetrical
earth
fault
80°C – 200°C for 1 c kA rms 2.00 3.20 3.60 3.90 5.80 6.50 7.10 7.80 11.10 12.50 13.60 19.10 21.30 23.70
Short circuit current rating for any other time (T) in the range 0.2 c to 5 c can be obtained by dividing the 1 c value by √T. For short circuit durations of less than 0.2 c, it is recommended that the 0.2 c rating be ud in order to prevent the possibility of cable damage by electromagnetic forces.
Ratings for armoured cables assume touching trefoil arrangement and armour bonded at both ends of the route.
* Circular
conductor.
! Sectoral conductor.
General Note
AEI Cables rerves the right to amend the product information without notice or liability.
The information is considered accurate at the time of going to print.
© AEI Cables Limited Durham Road, Birtley, Chester-le-Street, County Durham DH3 2RA
Constructional and Electrical Performance Data
BS5467/BS6724 – 0.6/1.0kV – Two core
Aluminium
conductors
thermotting
insulated
armoured
cables AEI Cables Limited Nominal
area
of
conductor mm²
16.00*
25.00
35.00
50.00
70.00
95.00
Insulation
radial
thickness mm 0.70 0.90 0.90 1.00 1.10 1.10
Inner
sheath
radial
thickness mm 0.80 0.80 1.00 1.00 1.00 1.20
Galvanid steel armour wire diameter mm 1.25 1.25 1.60 1.60 1.60 2.00
Outer
sheath
radial
thickness mm 1.50 1.60 1.70 1.80 1.90 2.00
Overall
diameter
(Nom) mm 20.00 19.00 22.00 24.00 27.00 30.00
Cable
weight
(Nom) Kg/Km
650
700
1000
1150
1450
1950
Internal
bending
radius
(Min) mm 160 152 176 192 216 240
Armour resistance @ 20°C (Max) Ω/Km 4.00 4.10 2.90 2.60 2.30 1.60
Armour gross cross ctional area mm² 39 38 54 60 70 100
Armour
conductivity % 48 29 30 25 19 20
< conductor resistance @ 20°C (Max) Ω/Km 1.91
1.20
0.868
0.641
0.443
0.320
< conductor resistance @ 90°C (Max) Ω/Km 2.45
1.54
1.11
0.822
0.568
0.411
Inductance mH/Km 0.251 0.253 0.245 0.243 0.239 0.233
Reactance @ 50 Hz Ω/Km 0.079 0.080 0.077 0.076 0.075 0.073
Impedance @ 90°C Ω/Km 2.45
1.54
dbl
1.11
0.826
0.573
0.417
DC
voltage
drop mV/A/M 4.80 3.10 2.20 1.60 1.10 0.82
Single
pha
voltage
drop mV/A/M 4.80 3.10 2.20 1.65 1.15 0.84
Three
pha
voltage
drop mV/A/M
- - - - - -
Continuous current carrying capacity (Laid direct) A 108 138 165 196 241 288
Continuous current carrying capacity (Ducts) A 88 112 135 160 197 237
Continuous current carrying capacity (Air) A 95 122 149 180 227 279
归属感英文
Conductor
short
circuit
symmetrical
fault
90°C – 250°C for 1 c kA rms 1.50 2.40 3.30 4.70 6.60 8.90
Armour
short
circuit
asymmetrical
earth
fault
80°C – 200°C for 1 c kA rms 1.50+ 1.70 2.50 2.80 3.20 4.60
Short circuit current rating for any other time (T) in the range 0.2 c to 5 c can be obtained by dividing the 1 c value by √T. For short circuit durations of less than 0.2 c, it is recommended that the 0.2 c rating be ud in order to prevent the possibility of cable damage by electromagnetic forces.
* Circular
conductor.
+ Limited by the short circuit capacity of the conductor.
General Note
AEI Cables rerves the right to amend the product information without notice or liability.
The information is considered accurate at the time of going to print.
© AEI Cables Limited Durham Road, Birtley, Chester-le-Street, County Durham DH3 2RA
Constructional and Electrical Performance Data
BS5467/BS6724 – 0.6/1.0kV – Three core
Aluminium
conductors
thermotting
insulated
armoured
cables AEI Cables Limited Nominal
area
of
conductor mm² 16.00* 25.00 35.00 50.00 70.00 95.00 120.00 150.00 185.00 240.00 300.00
Insulation
radial
thickness mm 0.70 0.90 0.90 1.00 1.10 1.10 1.20 1.40 1.60 1.70 1.80
Inner
sheath
radial
thickness mm 0.80 1.00 1.00 1.00 1.00 1.20 1.20 1.40 1.40 1.40 1.60
Galvanid
steel
armour
wire
diameter mm 1.25 1.60 1.60 1.60 1.60 2.00 2.00 2.50 2.50 2.50 2.50
Outer
sheath
radial
thickness mm 1.60 1.70 1.80 1.80 1.90 2.10 2.20 2.30 2.40 2.60 2.70
Overall
diameter
(Nom) mm 21.00 23.00 25.00 28.00 31.00 35.00 39.00 43.00 47.00 52.00 56.00
Cable
weight
(Nom) Kg/Km 800 1100 1250 1500 1850 2500 2950 3850 4450 5350 6250
Internal
bending
radius
(Min) mm 168 184 200 224 248 280 312 344 376 416 448
Armour resistance @ 20°C (Max) Ω/Km 3.80 2.70 2.50 2.20 1.90 1.40 1.20 0.86 0.76 0.68 0.63
Armour gross cross ctional area mm² 41 58 64 72 84 119 131 181 206 230 250
Armour
conductivity % 50 44 35 29 23 23 21 24 22 18 16
< conductor resistance @ 20°C (Max) Ω/Km 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100
< conductor resistance @ 90°C (Max) Ω/Km 2.45 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.162 0.130
Inductance mH/Km 0.251 0.253 0.245 0.243 0.239 0.233 0.232 0.233 0.234 0.232 0.229
Reactance @ 50 Hz Ω/Km 0.079 0.080 0.077 0.076 0.075 0.073 0.073 0.073 0.074 0.073 0.072
Impedance @ 90°C Ω/Km 2.45 1.54 1.11 0.826 0.573 0.417 0.333 0.275 0.223 0.178 0.149
DC
voltage
drop mV/A/M
- - - - - - - - - - -
Single
pha
voltage
drop mV/A/M
- - - - - - - - - - -
Three
pha
voltage
drop mV/A/M 4.20 2.70 1.95 1.45 0.97 0.72 0.58 0.47 0.39 0.31 0.26
Continuous
current
carrying
capacity
(Laid
rangefrom
direct) A 91 116 139 165 203 244 278 311 353 409 461
Continuous
current
carrying
capacity
(Ducts) A 74 95 113 135 167 201 230 259 294 342 386
Continuous
current
carrying
capacity
(Air) A 81 106 129 157 198 244 283 324 375 444 508
Conductor
short
circuit
symmetrical
fault
90°C – 250°C for 1 c kA rms 1.50 2.40 3.30 4.70 6.60 8.90 11.30 14.10 17.40 22.60 28.20
Armour
short
circuit
英语四级多少分算过asymmetrical
earth
fault
80°C – 200°C for 1 c kA rms 1.50+ 2.40+ 2.90 3.30 3.90 5.50 6.00 8.30 9.50 10.60 11.50
Short circuit current rating for any other time (T) in the range 0.2 c to 5 c can be obtained by dividing the 1 c value by √T. For short circuit durations of less than 0.2 c, it is recommended that the 0.2 c rating be ud in order to prevent the possibility of cable damage by electromagnetic forces.
* Circular
conductor.
+ Limited by the short circuit capacity of the conductor.
General Note
AEI Cables rerves the right to amend the product information without notice or liability.
The information is considered accurate at the time of going to print.
© AEI Cables Limited Durham Road, Birtley, Chester-le-Street, County Durham DH3 2RA
Constructional and Electrical Performance Data
BS5467/BS6724 – 0.6/1.0kV – Four core
Aluminium
conductors
thermotting
insulated
armoured
cables AEI Cables Limited Nominal
area
of
conductor mm² 16.00* 25.00 35.00 50.00 70.00 95.00 120.00 150.00 185.00 240.00 300.00
Insulation
radial
thickness mm 0.70 0.90 0.90 1.00 1.10 1.10 1.20 1.40 1.60 1.70 1.80
Inner
sheath
radial
thickness mm 0.80 1.00 1.00 1.00 1.20 1.20 1.40 1.40 1.40 1.60 1.60
Galvanid
steel
armour
wire
diameter mm 1.25 1.60 1.60 1.60 2.00 2.00 2.50 2.50 2.50 2.50 2.50
Outer
sheath
radial
thickness mm 1.60 1.70 1.80 1.90 2.10 2.20 2.30 2.40 2.60 2.70 2.90
Overall
diameter
(Nom) mm 22.00 26.00 28.00 31.00 36.00 39.00 44.00 48.00 53.00 59.00 64.00
Cable
关于爱的英语作文
weight
(Nom) Kg/Km 900 1250 1500 1800 2550 3050 4000 4650 5500 6650 7750
Internal
bending
radius
(Min) mm 176 208 224 248 288 312 352 384 424 472 512charice pempengco
Armour resistance @ 20°C (Max) Ω/Km 3.40 2.40 2.20 1.90 1.30 1.20 0.82 0.74 0.67 0.59 0.54
Armour
gross
cross
ctional
area mm² 46 66 72 82 122 135 191 211 235 265 289
Armour
conductivity % 56 50 39 34 34 27 31 28 24 21 19
< conductor resistance @ 20°C (Max) Ω/Km 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100
< conductor resistance @ 90°C (Max) Ω/Km 2.45 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.162 0.130
Inductance mH/Km 0.251 0.253 0.245 0.243 0.239 0.233 0.232 0.233 0.234 0.232 0.229
Reactance @ 50 Hz Ω/Km 0.079 0.080 0.077 0.076 0.075 0.073 0.073 0.073 0.074 0.073 0.072
Impedance @ 90°C Ω/Km 2.45 1.54 1.11 0.826 0.573 0.417 0.333 0.275 0.223 0.178 0.149
DC
voltage
drop mV/A/M
- - - - - - - - - - -
Single
pha
voltage
drop mV/A/M
- - - - - - - - - - -
Three
pha
voltage
drop mV/A/M 4.20 2.70 1.95 1.45 0.97 0.72 0.58 0.47 0.39 0.31 0.26
Continuous
current
carrying
capacity
(Laid
direct) A 91 116 139 165 203 244 278 311 353 409 461
Continuous
current
carrying
capacity
(Ducts) A 74 95 113 135 167 201 230 259 294 342 386
Continuous
current
carrying
capacity
(Air) A 81 106 129 157 198 244 283 324 375 444 508
Conductor
short
circuit
symmetrical
fault
90°C – 250°C for 1 c kA rms 1.50 2.40 3.30 4.70 6.60 8.90 11.30 14.10 17.40 22.60 28.20
Armour
short
circuit
asymmetrical
earth
fault
80°C – 200°C for 1 c kA rms 1.50+ 2.40+ 3.30+ 3.80 5.60 6.20 8.80 9.70 10.80 12.20 13.30
Short circuit current rating for any other time (T) in the range 0.2 c to 5 c can be obtained by dividing the 1 c value by √T. For short circuit durations of less than 0.2 c, it is recommended that the 0.2 c rating be ud in order to prevent the possibility of cable damage by electromagnetic forces.
* Circular
conductor.
颜色配搭+ Limited by the short circuit capacity of the conductor.
.