Electrically Operated Unitary Heat Pumps: Minimum Efficiency Requirements | ||||
Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency |
Air-cooled (cooling mode) | <65,000 Btu/h | All | Split system | 14 SEER; 11 EER; 8.2 HSPF (three pha) |
14.5 SEER; 12 EER; 8.2 HSPF (single pha) | ||||
Single package | 14 SEER; 11 EER; 8.0 HSPF (three pha) | |||
14 SEER; 11 EER; 8.0 HSPF (single pha) | ||||
≥65,000 Btu/h and <135,000 Btu/h | Electric resistance (or none) | Split system and single package | 11.3 EER; 11.4 IEER; 3.35 COP | |
≥135,000 Btu/h and <240,000 Btu/h | Electric resistance (or none) | Split system and single package | 10.9 EER; 11 IEER; 3.25 COP | |
≥240,000 Btu/ha | Electric resistance (or none) | Split system and single package | 9.5 EER; 10.6 IEER | |
Geothermal, clod loop water-to-air | 17.1 EER; 3.6 COP (single pha) | |||
Geothermal, open loop water-to-air | 21.1 EER; 4.1 COP (single pha) | |||
Geothermal, clod loop water-to-water | 16.1; 3.1 COP (single pha) | |||
Geothermal, open loop water-to-water | 20.1; 3.5 COP (single pha) | |||
Geothermal, DGX | 16.0 EER; 3.6 COP (single pha) | |||
a Heat pumps with size equal to or greater than 240,000 Btu/h are not covered by federal purchasing requirements. Minimum efficiency prented is consistent with ASRHAE 90.1-2013. | ||||
Electrically Operated Unitary Air Conditioners: Minimum Efficiency Requirements | ||||
Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency |
Air conditioners, air-cooled | <65,000 Btu/h | All | Split system | 14.5 SEER and 12 EER (single pha) |
14 SEER and 12 EER (three pha) | ||||
Single package | thornheart14 SEER and 11 EER (single pha) | |||
14 SEER and 11 EER (three pha) | ||||
≥65,000 Btu/h and <135,000 Btu/h | Electric resistance (or none) | Split system and single package | 11.7 EER and 11.8 IEER | |
All other | Split system and single package | 11.5 EER and 11.6 IEER | ||
≥135,000 Btu/h and <240,000 Btu/h | Electric resistance (or none) | Split system and single package | 11.7 EER and 11.8 IEER | |
All other | Split system and single package | 11.5 and 11.6 IEER | ||
≥240,000 Btu/h and <760,000 Btu/ha | Electric resistance (or none) | Split system and single package | 12.4 EER and 13.6 IEER | |
All other | Split system and single package | 12.2 EER and 13.4 IEER | ||
≥760,000 Btu/ha | Electric resistance (or none) | Split system and single package | 12.2 EER and 13.5 IEER | |
All other | Split system and single package | 12.0 EER and 13.3 IEER | ||
a Air conditioners with size equal to or greater than 240,000 Btu/h are not covered by federal purchasing requirements. Minimum efficiency prented is consistent with ASRHAE 90.1-2013. | ||||
Gas- and Oil-Fired Boilers: Minimum Efficiency Requirements | ||||
Equipment Type | Subcategory or Rating Condition | Size Category (Input) | Efficiency Metric | Minimum Efficiency |
Boilers, hot water | Gas-fired | <300,000 Btu/h | AFUE | 90% |
≥300,000 Btu/h and ≤2,500,000 Btu/h | Eta | 94% | ||
>2,500,000 Btu/h and ≤10,000,000 Btu/h | Et | 94% | ||
>10,000,000 Btu/hb | Ec | 82% | ||
Oil-fired | <300,000 Btu/h | twice怎么读 AFUE | assign是什么意思87%nessie | |
≥300,000 Btu/h and <2,500,000 Btu/h | Et | 85.5% | ||
>2,500,000 Btu/h and ≤10,000,000 Btu/h | Et | 85.5% | ||
>10,000,000 Btu/hb | Ec | 84% | ||
Boilers, steam | Gas-fired | <300,000 Btu/h | AFUE | 90% |
Gas-fired (all, except natural draft) | ≥300,000 Btu/h and ≤2,500,000 Btu/h | april缩写Et | 80% | |
>2,500,000 Btu/h and ≤10,000,000 Btu/h | Et | 80% | ||
>10,000,000 Btu/hb | Et | 79% | ||
Gas-fired, natural draft | ≥300,000 Btu/h and ≤2,500,000 Btu/h | Et | 80% | |
>2,500,000 Btu/h and ≤10,000,000 Btu/h | Et理臣教育 | 80% | ||
>10,000,000 Btu/hb | Et | 77% | ||
Oil-fired | <300,000 Btu/h | AFUE | 87% | |
≥300,000 Btu/h and ≤2,500,000 Btu/h | Et | 83.5% | ||
>2,500,000 Btu/h and ≤10,000,000 Btu/h | Et | 83.5% | ||
>10,000,000 Btu/hb | Et | 81% | ||
a Thermal efficieny (Et) is bad on Hydronics Institute, Method to Determine Efficiency of Commercial Space Heating Boilers (HI BTS-2000, Rev. 06.07). b Boilers with input greater than 10,000,000 Btu/h are not covered by federal purchasing requirements. Minimum efficiency prented is consistent with ASRHAE 90.1-2013 Table 6.8.1-6. | ||||
Water-Chilling Packages: Minimum Efficiency Requirements | ||||
Equipment Type | Size Category | Units | Minimum Efficiency | |
Path A (Full-Load Optimized Applications) | Path B (Part-Load Optimized Applications) | |||
Air-cooled | <150 t | EER (Btu/W) | ≥10.40 FL | ≥9.56 FL |
≥12.50 IPLV | ≥15.39 IPLV | |||
Air-cooled | ≥150 t | EER (Btu/W) | ≥10.40 FL | ≥9.56 FL |
≥12.75 IPLV | ≥15.07 IPLV | |||
Water-cooled, electrically operated positive displacement | < 75 t | kW/t | ≤0.75 FL | ≤0.80 FL |
≤0.63 IPLV | ≤0.60 IPLV | |||
Water-cooled, electrically operated positive displacement | ≥75 t and <150 t | kW/t | ≤0.71 FL | ≤0.79 FL |
≤0.61 IPLV | ≤0.51 IPLV | |||
Water-cooled, electrically operated positive displacement | ≥150 t and <300 t | kW/t | ≤0.68 FL | ≤0.72 FL |
≤0.58 IPLV | ≤0.50 IPLV | |||
Water-cooled, electrically operated positive displacement | ≥ 300 t and <600 t | kW/t | ≤0.58 FL | ≤0.64 FL |
≤0.54 IPLV 新生儿护理知识 | ≤0.48 IPLV | |||
Water-cooled, electrically operated positive displacement | ≥600 t | kW/t | ≤0.58 FL | ≤0.64 FL |
≤0.54 IPLV | ≤0.48 IPLV | |||
Water-cooled, electrically operated centrifugal | < 150 t | kW/t | ≤0.62 FL | ≤0.64 FL |
≤0.60 IPLV | ≤0.36 IPLV | |||
Water-cooled, electrically operated centrifugal | ≥150 t and <300 t | kW/t | ≤0.59 FL | ≤0.64 FL |
≤0.60 IPLV | ≤0.35 IPLV | |||
macromedia |