BWY(WTYK)-802,803 SERIES
TRANSFORMER TEMPERATURE CONTROLLER
DESCRIPTION & OPERATION INSTRUCTIONS
HANGZHOU HUALI INSTRUMENT & METER CO.,LTD
TEL EXCHANGE: 0086-571-87423833
SALES DEPT:0086-571-87088120
FAX:0086-571-87919920
ADDRESS:27 Longwu Industrial Zone, Hangzhou
E-mail:***************.zj
Http://
THANKS FOR USING OUR PRODUCTS
PLEASE READ THE DIRECTIONS BEFORE USE
INDEX
1.General Survey………………………………………………………………………………………(1)艺考生文化课复习
2.Working Principle …………………………………………………………………………………(5)
3.Principle Technical Specification……………………………………………………………………(5)
4.Installing & Operation …………………………………………………………………………… (6)
5.Points for Attention ………………………………………………………………………………(10)
6.Appendix Pt100 Industrial Platinum Resistance Scale Value ……………………………………(11)
1 General Survey
1. The type of temperature controller is defined in accordance with the standard named "Transformer Pressure-type Thermometer" formulated by the Transformer Rearch Institute in ShenYang.
2. The type of temperature controller is defined in accordance with the standard named "The Principle of Type Organization of Industrial Automatic Instrument"
2
W T Y K – 80 3 A (TH) / 288 F C
BWY(WTYK)-802,803 SERIES TEMPERATURE CONTROLLER
COMPLETE SETS AND ITS APPLICATION
No | TYPE & NAME | MAIN USEAGE | SUITABLE SITE | REEE |
1 | BWY(WTYK)-802,803 Transformer Temperature Controler | Measuring the oil temperature on the top of transformer and switch on the motor of cooler and alarm when temperature is over the pret value(refer to figure 1) | For transformer capacity more than 1000kVA | |
2 | BWY(WTYK)-802,803(TH)Transformer Temperature Controller | Same as No1 And is available in damp and hot site | For transformer capacity more than 1000kVA | human hair |
3 | BWY(WTYK)-802,803A(TH)Transformer Temperature Controller | Same as No2 Adopting the technical in transducer of complex temperature and can simultaneously nd out the signal of Pt100 platinum thermal resistor | For transformer capacity more than 800kVA | |
4 | XMT-288F Numberical Temperature Control Instrument | Form a complete t with BWY(WTYK)-802A,803A(TH)to attain telemetering temperature and remote control(refer to figure 2)Square inlaid panel type The mountimg dimension is same as XCT | For transformer capacity more than 8000kVA | |
5 | 中国教育教师网XMT-288FC Numberical Temperature Control Instrument | Form a complete t with BWY(WTYK)- 802A,803A(TH)to attain telemeterimg temperatu-re and remote control and also can output direct current standard signal of 0-5V 1-5V or 4-20mA for computer | For transformer capacity more than 8000kVA | |
6 | BWY(WTYK)-802,803A(TH)/288F transformer temperature control instrument t | Same as No3,4 can simuataneously replace 1)WTZK-02 temperature controller 2)Resistance thermometer 3)Change-over switch | For transformer capacity more than 8000kVA | |
7 | BWY(WTYK)-802,803A(TH)/288FC transformer temperature control instrument t | Same as No3,5 can simultaneously replace 1)WTZK-02 temperature control-ler 2)Resistance thermometer 3)Change-over switch 4)XCTmovable coil thermometer 5)The transformer of signal | For transformer capacity more than 8000kVA of lr-rvice power station | |
| | | | |
2 WORKING PRINCIPAL
The transformer temperature controller(which is refered as temperature controller bellow)is consist of elastic component , capillary tube and temperature bulb. It is a aled system filled with temperature-nsing medium.When the measured temperature changes the volume of actuating medium in the temperature bulb will be changed along with linear graduation. This volume increment is transmitted by capillary tube so as to take a corresponding lineardisplacement. After magnifying the linear displacement by a special amplifier, the measured temperature can be indicated and switch on a micro switch to nd out a electric signal to power on or off the cooler system.
Like The BWY(WTYK)-803A temperature controllers, the BWY(WTYK)-802A temperature controller adopts the technology of complex transducing which can output the signal of Pt100 platinum thermal resistor simultaneously. This signal can be transmitted to a controller room more than hundreds of meters away. By the rics XMT digital display thermometer, the temperature of transformer will be displayed and adjusted
学业水平考试报名系统>spontaneouslyat the same time. The signal also can be translated to computer typical signal(0~5V 1~5V or 4~20mA)by a digital themometer.
profitmargin3 TECHNICAL SPECIFICATION
3.1 BWY(WTYK)-802, 803
1 Normal working condition: (-40~+55)℃
2 Measuring scope: (-20~+80)℃
(0~+100)℃
(0~+120)℃
3 Indicative accuracy: 1.5grade
4 Controlling capability:
Setting range: adjustable within the work span
Setting accuracy: ±3℃
Switch difference: 6±2℃
Rated power: AC250V 3A
Standard tting point:
BWY(WTYK)-802: K1=55℃ K2=80℃
dean potterBWY(WTYK)-803: K1=55℃ K2=65℃ K3=80℃
5 The outline drawing and monnting dimension refer to figue 1
3.2 BWY(WTYK)-802, 803A
1 Normal working condition: (-40~+55)℃
2 Measuring scope: (-20~+80)℃
(0~+100)℃
(0~+120)℃
3 Indicative accuracy: 1.5grade
4 Controlling capability:
Setting range: adjustable within the work span
Setting accuracy: ±3℃
Switch difference: 6±2℃
Rated power: AC250V 3A
Standard tting point:
BWY(WTYK)-802A: K1=55℃ K2=80℃
BWY(WTYK)-803A: K1=55℃ K2=65℃ K3=80℃
5 The outline drawing and monnting dimension refer to figue 1
6 Output signal of pt100 platinum thermal resistor(refer as appendix table)
3.3 XMT-288F digital display thermometer
working
(for details e the additional instruction)
红旗飘飘引我成长征文3.4 XMT-288FC digital display thermometer
(for details e the additional instruction)
4 INSTALLING & OPERATION INSTRUCTION
4.1 BWY(WTYK)-802, 803
1 PERSET THE SWITCH
The default values of two switches of WTYK-802 are:K1=55℃ K2=80℃ while the three of WTYK-803 are: K1=55℃ K2=65℃ K3=80℃. Following is how to pret the switch position when needed.
Open the cover of guage(refer as figure 4), loon the green screw, move the red indicative needle to new pret value and then screw the green screw. At last clo the guage cover.