Technical Data
初中英语作文带翻译
贾斯丁比伯的歌曲1321 Power Conditioning Products单程票英语
Don’t Ignore the Cost of Power Line Disturbance
Topic Page
Product Overview2
武汉英语学校1321-3R and 3RA Series Line Reactors3
1321 Reflective Wave Reduction (RWR) Devices12
1321-3TH/3TW Series Three-Pha Isolation Transformers16
1321-M Common Mode Chokes21
1321-DC DC Link Chokes24
2Rockwell Automation Publication 1321-TD001O-EN-P - September 2012
1321 Power Conditioning Products
Additional Resources
The documents contain additional information concerning related products from Rockwell Automation.
Y ou can view or download publications /literature/. T o order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales reprentative.For Allen-Bradley Drives T echnical Support:
aromanice
Product Overview
Allen-Bradley reactors help keep equipment running longer by absorbing many of the power line disturbances which can shut down your drive. Allen-Bradley isolation transformers can provide both voltage change and isolation for your variable speed drive. The designs are harmonic compensated and IGBT protected to assure optimum performance in the prence of harmonics.
Resource
Description
Wiring and Grounding Guidelines for Pul Width Modulated (PWM) AC Drives, publication DRIVES-IN001
Provides basic information needed to properly wire and ground PWM AC drives.Safety Guidelines for the Application, Installation and Maintenance of Solid
小高考查分State Control, publication SGI-1.1
Provides general guidelines for the application, installation, and maintenance of solid-state control.
Title
Online at…
Allen-Bradley Drives Technical Support
bring the future /support/abdrives or call (1) 262.512.8176
Rockwell Automation Publication 1321-TD001O-EN-P - September 20123
1321 Power Conditioning Products
1321-3R and 3RA Series Line Reactors
Applying Allen-Bradley Line Reactors At the Input of the Drive
cipherAt the input of a drive, line reactors help protect against surges or spikes on the incoming power lines and help reduce harmonic distortion.At the Output of the Drive
In long motor lead applications, Allen-Bradley load reactors located between the drive and motor help reduce dv/dt and motor terminal peak voltages. The u of a load reactor also helps protect the drive from surge currents caud by rapid changes in the load.
With Multiple Drives
Multiple drives on a common power line should each have their own line reactor. Individual line reactors provide filtering between each drive to help reduce any crosstalk while providing optimum surge protection for each drive.
With Multiple Motors
When more than one motor is controlled by a single drive, a single line reactor can typically be ud between the drive and all the motors. Size the line reactor bad on the total motor/load horpower.
uma
With Single-Pha Input
A three-pha reactor can be ud for single-pha applications by routing each of the two input power conductors to the outside two coils, and leaving the center coil disconnected. The sum of the inductance of the two coils is the total inductance applied to the circuit. Contact Rockwell Automation
T echnical Support for assistance in specifying the proper reactor.
•Eliminate Nuisance T ripping •Improve T rue Power Factor •Extend Semiconductor Life •Reduce Voltage Notching •Reduce Harmonic Distortion
•Meet IEEE-519 or EN-61800
•Protect Motors from Long Lead Effects •Reduce Surge Currents •Reduce Output Voltage dv/dt •Reduce Motor T emperature •Extend Semiconductor Life
•Reduce Audible Motor Noi
1321 Power Conditioning Products
Selecting the Correct Impedance Rating
Why is the Right Impedance Rating Important?
Selecting the correct impedance rating is critical for your job. An impedance value too low may not limit peak current. T oo high of an impedance may reduce input voltage. Allen-Bradley line reactors offer two impedance ratings.
3% Impedance Rated Reactors to Reduce Nuisance Trips
Allen-Bradley line reactors rated at 3% are typically sufficient to absorb line spikes and motor current surges and will help prevent nuisance tripping of drive and circuit breakers in most applications.
5% Impedance Rated Reactors to Reduce Harmonic Contentcutdown
Allen-Bradley reactors rated at 5% are best for reducing harmonic current and frequencies. The line reactors help comply with IEEE-519 (not normally ud as load reactors).
Voltage Spike Protection
Voltage spikes on AC power lines can cau elevation of the DC bus voltage which may cau the drive to trip on an overvoltage condition.
3% impedance reactors are very effective at protecting drives against voltage spikes and nuisance tr
ipping. Allen-Bradley line reactors absorb the line spikes protecting the drive from nuisance tripping and damage.
Motor Protection
Allen-Bradley load reactors can help protect motors from high peak voltages.
For IGBT drive applications with long drive-to-motor lead lengths, Allen-Bradley load reactors can help protect against fast dv/dt ri times.
4Rockwell Automation Publication 1321-TD001O-EN-P - September 2012
1321 Power Conditioning Products Catalog Number Explanation
Rockwell Automation Publication 1321-TD001O-EN-P - September 20125