Diagnostic Messages
In addition to the output, the LCD meter displays abbreviated operation, error,
and warning messages for troubleshooting the transmitter. Messages appear according to their priority, with normal operating messages appearing last. To
字体文件determine the cau of a message, u a Model 275 HART Communicator to further interrogate the transmitter. A description of each LCD diagnostic message follows.
borregoError
Error messages appear on the LCD meter display to inform you of rious
problems effecting the operation of the transmitter. The meter displays an
error message until the error condition is corrected, and the analog output is
driven to the specified alarm level. No other transmitter information is
displayed during an alarm condition.
1、FAIL
The transmitter CPU board and the nsor module are incompatible. If you encounter this message, contact Romount Customer Central at
800-999-9307 if you need assistance.
2、Fail Module
The nsor module is disconnected or is malfunctioning. Verify that the
nsor module ribbon cable is connected to the back of the electronics board. If the ribbon cable is properly connected, there is a problem within
the nsor module. Possible sources of problems include:
• Pressure or temperature updates are not being received in the nsor module.
• A non-volatile memory fault that will effect transmitter
operation has been detected in the module by the memory verification routine.
樱花日语
Some non-volatile memory faults are ur-repairable. U a Model 275 HART Communicator to diagno the error and determine if it is repairable. Any error message that ends in “FACTORY” is not repairable. In cas of non ur-repairable errors, you must replace the nsor module. See “Disasmbly Procedures” on page 5-3 or contact
Romount Customer Central at 800-999-9307 if you need assistance.
3、Fail Elect
The transmitter electronics board is malfunctioning due to an internal fault. Some of the FAIL ELECT errors are ur-repairable. U a Model 275
HART Communicator to diagno the error and determine if it is repairable. Any error message that ends in “FACTORY” is n ot repairable.
In cas of non ur-repairable errors, you must replace the electronicsemotiona什么意思
board. See “Disasmbly Procedures” on page 5-3 or contact Romount Customer Central at 800-999-9307 if you
need assistance.
4、Fail Config托福是什么
A memory fault has been detected in a location that could effect transmitter operation, and is ur-accessible. To correct this problem, u
a Model 275 HART Communicator to interrogate and reconfigure the appropriate portion of the transmitter memory. Contact Romount
Customer Central at 800-999-9307 if you need assistance.
Warnings
gladtomeetyouWarnings appear on the LCD display to alert you of ur-repairable problems
with the transmitter, or current transmitter operations. Warnings appear
alternately with other transmitter information until the warning condition is
corrected or the transmitter completes the operation that warrants the warning message.
1、Press Limit
The process variable read by the transmitter is outside of the transmitter’s
range.
2、Temp Limit
尺子英语怎么读
The condary temperature variable read by the transmitter is outside of
the transmitter’s range.
3、Curr Fixed
The transmitter is in multidrop mode. The analog output is not tracking pressure changes.
4、Curr Saturd
The pressure read by the module is outside of the specified range, and the analog output has been driven to saturation levels.
5、Loop Test
2020年高考语文答案>voltage是什么意思A loop test is in progress. During a loop test or 4–20 mA trim, the analog output is t to a fixed value. The meter display alternates between the current lected in milliamps and “LOOP TEST.”
6、Xmtr Info
A non-volatile memory fault has been detected in the transmitter memory by the memory verification routine. The memory fault is in a location containing transmitter information. To correct this problem, u a Model 275 HART Communicator to interrogate and reconfigure the appropriate portion of the transmitter memory. This warning does not effect the transmitter operation. Contact Romount Customer Central at
800-999-9307 if you need assistance.
Operation
Normal operation messages appear on the LCD meter to confirm actions or inform you of transmitter status. Operation messages are displayed with other transmitter information, and warrant no action to correct or alter the transmitter ttings.
1、Zero Pass
The zero value, t with the local zero adjustment button, has been accepted by the transmitter, and the output should change to 4 mA.
2、Zero Fail
The zero value, t with the local zero adjustment button, exceeds the maximum rangedown allowed for a particular range, or the pressure nd by the transmitter exceeds the nsor limits.
3、Span Pass
The span value, t with the local span adjustment button, has been accepted by the transmitter, and the output should change to 20 mA.
4、Span Fail
The span value, t with the local span adjustment button, exceeds the maximum rangedown allowed for a particular range, or the pressure nd by the transmitter exceeds the nsor limits.
5、LOCAL DSBLD
This message appears during reranging with the integral zero and span buttons and indicates that the transmitter local zero and span adjustments have been disabled. The adjustments may have been disabled by the transmitter curity jumper on the transmitter circuit board or through software commands from the Model 275. See “Security (Write Protect)” on page 2-14 for information on the position of the curity jumper and information on software lockout.
如何锻炼心理素质
6、Write Protect
This message appears if you attempt to change the transmitter configuration data while the curity jumper is in the ON position. See “Security (Write Protect)” on page 2-14 for more information about the curity jumper.