Induction motor starting methods and issues
asynctaskJ Larabee ,B Pellegrino ,B Flick
Abstract -Many methods can be ud to start large AC induction motors. Choices such as full voltage, reduced voltage either by autotransformer or Wyes - Delta, a soft starter, or usage of an adjustable speed drive can all have potential advantages and trade offs. Reduced voltage starting can lower the starting torque and help prevent damage to the load. Additionally, power factor correction capacitors ca
n be ud to reduce the current, but care must be taken to size them properly. Usage of the wrong capacitors can lead to significant damage. Choosing the proper starting method for a motor will include an analysis of the power system as well as the starting load to ensure that the motor is designed to deliver the needed performance while minimizing its cost. This paper will examine the most common starting methods and their recommended applications.
dozoI. INTRODUCTION
There are veral general methods of starting induction motors: full voltage, reduced voltage, wyes-delta, and part winding types. The reduced voltage type can include solid state starters, adjustable frequency drives, and autotransformers. The, along with the full voltage, or across the line starting, give the purchar a large variety of automotives when it comes to specifying the motor to be ud in a given application. Each method has its own benefits, as well as performance trade offs. Proper lection will involve a thorough investigation of any power system constraints, the load to be accelerated and the overall cost of the equipment.
In order for the load to be accelerated, the motor must generate greater torque than the load requirement. In general there are three points of interest on the motor's speed-torque curve. The first
is locked-rotor torque (LRT) which is the minimum torque which the motor will develop at rest for all angular positions of the rotor. The cond is pull-up torque (PUT) which is defined as the minimum torque developed by the motor during the period of acceleration from rest to the speed at which breakdown torque occurs. The last is the breakdown torque (BDT) which is defined as the maximum torque which the motor will develop. If any of the points are below the required load curve, then the motor will not start.tinyos
The time it takes for the motor to accelerate the load is dependent on
the inertia of the load and the margin between the torque of the motor and the load curve, sometimes called accelerating torque. In general, the longer the time it takes for the motor to accelerate the load, the more heat that will be generated in the rotor bars, shorting ring and the stator winding. This heat leads to additional stress in the parts and can have an impaction motor life.
II. FULL VOL TAGE
The full voltage starting method, also known as across the line starting, is the easiest method to employ, has the lowest equipment costs, and is the most reliable. This method utilizes a control to cl
come homeo a contactor and apply full line voltage to the motor terminals. This method will allow the motor to generate its highest starting torque and provide the shortest acceleration times.
This method also puts the highest strain on the power system due to the high starting currents that can be typically six to ven times the normal full load current of the motor. If the motor is on a weak power system, the sudden high power draw can cau a temporary voltage drop, not only at the motor terminals, but the entire power bus feeding the starting motor. This voltage drop will cau a drop in the starting torque of the motor, and a drop in the torque of any other motor running on the power bus. The torque developed by an induction motor varies roughly as the square of the applied voltage. Therefore, depending on the amount of
voltage drop, motors running on this weak power bus could stall. In addition, many control systems monitor under voltage conditions, a cond potential problem that could take a running motor offline during a full voltage start. Besides electrical variation of the power bus, a potential physical disadvantage of an across the line starting is the sudden loading en by the driven equipment. This shock loading due to transient torques which can exceed 600% of the locked rotor torque can increa the wear on the equipment, or even cau a catastrophic failure if the load can not handle the torques generated by themotor during staring.
A. Capacitors and Starting
Induction motors typically have very low power factor during starting and as a result have very large reactive power draw. See Fig. 2. This effect on the system can be reduced by adding capacitors to the motor during starting.
The large reactive currents required by the motor lag the applied voltage by 90 electrical degrees. This reactive power doesn't create any measurable output, but is rather the energy required for the motor to function. The product of the applied system voltage and this reactive power component can be measured in V ARS (volt-ampere reactive). The capacitors act to supply a current that leads the applied voltage by 90 electrical degrees. The leading currents supplied by the capacitors cancel the lagging current demanded by the motor, reducing the amount of
reactive power required to be drawn from the power system.朋友的英文
To avoid over voltage and motor damage, great care should be ud to make sure that the capacitors are removed as the motor reaches rated speed, or in the event of a loss of power so that the motor will not go into a generator mode with the magnetizing currents provided from the capacitors. This will be expanded on in the next ction and in the appendix.
B. Power Factor Correction
财务预算编制Capacitors can also be left permanently connected to rai the full load power factor. When ud in this manner they are called power factor correction capacitors. The capacitors should never be sized larger than the magnetizing current of the motor unless they can be disconnected from the motor in the event of a power loss.
过去完成时练习题及答案The addition of capacitors will change the effective open circuit time constant of the motor. The time constant indicates the time required for remaining voltage in the motor to decay to 36.8% of rated voltage after the loss of power. This is typically one to three conds without capacitors.
With capacitors connected to the leads of the motor, the capacitors can continue to supply magnetizing current after the power to the motor has been disconnected. This is indicated by a longer time constant for the system. If the motor is driving a high inertia load, the motor can change