Draining_water_from_an_E2760FA

更新时间:2023-05-21 06:08:06 阅读: 评论:0

Service 7.1.4 Documentation > Cooling Unit Guide > Maintaining the Cooling System E2760FA/FC/FAL > Exchanging water
Task
Draining water from an E2760FA/FALjea
Procedure
1.Switch off power to the cooling system. See Lockout/Tagout Procedure.
鲜为人知是什么意思>三星i908e广告2.Open the manual filling valve (red tap) at the rear of the cooling system by turning it into the horizontal position. See the figure below.
a.Remove the plug from the manual filling inlet, e below.
3.Drain the cooling system (includes the water tank).
certainly怎么读a.Place a drip pan under the drain taps.
b.Connect a drain ho to the Water Drain outlet (blue tap), e the figure below.
c.Place the drain ho into the drip pan or a canister.
d.Open the blue tap and drain the cooler. This procedure is written for the E2760FA, but applies equally to the E270FAL.
By activating the flush mode before draining the cooling unit you can drain last traces of water from the cooling unit. Refer to Hidden options - flushing, diagnostic and restore. The flush mode is not
available on E2760FAL.
英文铃音>谷歌在线翻译英语
4.Drain the condary loop pipe work.
a.Place a drip pan next to the water connections.
b.Connect the drain ho asmbly E2760-67356 to the "From System" and "To System" couplers
and drain the remaining water in the pipes into the drip pan. Refer to the next figure.
c.When no more water comes out remove the drain ho asmbly.
calloneUp to 30 liters (approx. 8 US gallons) of water will drain off.
5.Drain the primary loop pipe work.
a.Remove the insulation cap from the "From Plant" drain valve (red tap). The cap prevents water
condensing on the outside of the valve.
b.Place a drip pan under the "From Plant" and "To Plant" drain taps.
matchc.Open both red taps.
6.When no more water comes out clo the taps.
7.Replace the insulation cap on the "From Plant" drain valve (red tap).
8.Clo the red tap for manual filling.
9.Wipe off any spilled water with absorbent tissues.
温度单位When you have completed any maintenance or rvicing work. refill the cooling system with drinking quality fresh water. See Filling the Cooling System with Water for instructions.
Functional changes
外文资料E2760FAL cooling unit introduced
Service 7.1.4 Documentation Topic 89444

本文发布于:2023-05-21 06:08:06,感谢您对本站的认可!

本文链接:https://www.wtabcd.cn/fanwen/fan/90/116705.html

版权声明:本站内容均来自互联网,仅供演示用,请勿用于商业和其他非法用途。如果侵犯了您的权益请与我们联系,我们将在24小时内删除。

下一篇:Drain auger
标签:意思   温度   资料   广告
相关文章
留言与评论(共有 0 条评论)
   
验证码:
Copyright ©2019-2022 Comsenz Inc.Powered by © 专利检索| 网站地图