热氟融霜工艺流程2009年04月08日
F1:Applications Modulating pressure and temperature regulators Hot gas defrosting  from top of  evaporator –direct expansion
This defrosting system is ud on commercial and industrial central refrigerating systems
with veral evaporators and direct expansion.
Product list
(1) PM 1 Main valve (shut-off valve)
(2) EVM On/off pilot
(3) TE 20 Thermostatic expansion valve
(4) PM 1 Main valve (shut-off valve)
(5) EVM On/off pilot
(6) PM 3 Main valve (modulating)
(7) CVPP (HP) Differential pressure pilot
(8) EVM On/off pilot
(9) NRVA Check valve
(11) NRVA Check valve
(12) PM 3 Main valve (modulating)定语后置的标志
(13) EVM On/off pilot摩羯座男生喜欢一个人的表现
etl工程师(14) CVQ Electric pilot (actuator)
(15) EKS 61: Electronic temperature regulator
血细胞包括什么(16) AKS 21M Pt 1000 _ air nsor
泾渭分明读音Function
Refrigerating pha Liquid pass through shut-off valve PM 1 (1)kept open by its pilot EVM (2).
Liquid injection occurs through thermostatic expansion valve TE 20 (3). Main valve PM 3 (12) modulates the evaporating pressure in order to maintain the  temperature
of the air being cooled.
The function is performed by CVQ pilot (14) which  is itlf controlled by electronic regulator EKS
正弦定理余弦定理61 (15) with air nsor AKS 21 M (16). Pilot valve EVM (13) is open. Main valve PM 3 (6) in the high-pressure line is kept open by pilot E~ Defrosting valve PM 1(4) is
kept clod by pilot EVM (5).
Defrosting pha
郁闷什么意思Main valves PM 1 (1), PM 3 (6) and PM 3 (12) are clod -each by their own EVM pilot.
Main valve PM 1 (4) is opened by EVM pilot (5) and feeds hot gas against the direction of  flow to the evaporators that need defrosting.
Setting
8核处理器Example
System with R22    The CVPP (HP) (7) is pret at between 1 and 1.5 bar.