0x8000401A
The rver process could not be started becau the configured identity is incorrect. Check the urname and password.
0x80004005
Unspecified Error
0x800706BA
RPC_S_SERVER_UNAVAILABLE
The RPC rver is unavailable
0x800706BF
远程过程调⽤失败且未执⾏
0x8007000E
E_OUTOFMEMORY
Not enough memory to complete the requested operation. This can happen any time the rver needs to allocate memory to complete the requested operation.
0x80070776
Couldn’t create connection with advi sink,
Reason for error: There is a problem resolving the computer name.
Solution: This problem can be solved by specifying the IP address of the rver instead of specifying the computer name
防辐射
0x80070005
三八图片0x80070005 appears in the OPC Client application when it succeeds in launching an OPC Server or OpcEnum, but fails to receive a reply from either of the applications. This error could be caud under veral conditions: On the OPC Server PC, the OPC Client Ur Account does not have the right Access Control List (ACL) permissions in the System-Wide DCOM ttings, Access Permissions, Edit Default.
On the OPC Client PC, the OPC Server Ur Account does not have the right Access Control List (ACL) permissions in the System-Wide DCOM ttings, Access Permissions, Edit Limits.
盘子画图片老人助听器怎么选On the OPC Client PC, the DCOM Default Impersonation Level is t to “Anonymous” instead of “Identify”, and the “ANONYMOUS LOGON” Access Control Entry (ACE) does not exist in the OPC Client PC, Access Control List (ACL) permissions in the System-Wide DCOM ttings, Access Permissions, Edit Limits.
0x80010108
RPC_E_DISCONNECTED
建筑安全事故0x80080005
Server Execution Failed
Failure to obtain a CLSID
OPC Client application failed to find the OPC Server. The two most common caus are:
1. Failure to find the OPC rver in the Windows Registry
2. Failure to connect to OPCENUM.EXE
Failed to connect to 2.0 data access interface for group … Falling back to 1.0 interface物业前台
个税怎么计算可能原因:计算机重名或局域⽹DNS服务故障,或者在不同⼦⽹中