1、进入欢迎画面(敲回车):
>Time, Message, Cancel, Hello? H
>Enter ur initials : HIGH
>Enter ur password : ????----------- (也输入HIGH)
09:00:12 08/23/2009 SUN Logged on successfully Field panel <MODBUSMEC>
Ur: <HIGH> <High default ur account> 南斯拉夫战争
2、进入功能选择:当然翻译
>Point, Application, Time, Message, Cancel, System, passWord, Bye? S
>Diagnostics, Urs, dAtes, deStinations, Error_msgs, Hardware, Text, Quit? H
>Fieldpanels, Ethernet, nodeNametable, Disks, Quit? F
>Log, Display, Add, dElete, Modify, Config, Quit? D
>Here, Printer
>Field panel name : MODBUSMEC---------------------
08/23/2009 SUN FIELD PANEL CONFIGURATION REPORT 09:01
-------------------------------------------------------------------------------
Field panel address : 0
Firmware revision : MCE1007a MEFE MBP2.7 704 V2.7 Apogee
销售经验Firmware checksum : 0000
MMI/MODEM : 9600 bps Modem disconnected
反应性低血糖MMI : 9600 bps
BLN : 9600 bps
Point modules : Disabled
FLN #1 : 19200 bps
FLN #2 : 9600 bps
FLN #3 : 9600 bps
Battery status : Alive
闹铃铃声确认单模板Language : English American
BLN name : EBLN
Site name : BAOJI
Node name : MODBUSMEC
云服务器怎么用
DNS Suffix :
IP Address : 192.168. 1.100
Netmask : 255.255.255. 0
微信公众平台注册 Gateway Address : 0. 0. 0. 0
DNS 1 : 0. 0. 0. 0
DNS 2 : 0.
DNS 3 : 0. 0. 0. 0
DNS 4 : 0. 0. 0. 0
MAC Address : 00:C0:E4:01:F2:4A
Configured Data Rate : Auto Negotiate
Configured Duplex : Auto
Actual Data Rate : 10BaT
Actual Duplex : Half
Link Status : Down
Telnet Enabled : Disabled
End of report
>Log, Display, Add, dElete, Modify, Config, Quit? Q
>Fieldpanels, Ethernet, nodeNametable, Disks, Quit? Q
>Diagnostics, Urs, dAtes, deStinations, Error_msgs, Hardware, Text, Quit? Q
>Point, Application, Time, Message, Cancel, System, passWord, Bye? B