GE MRI专用冷水机组PZAT18D(Legacy Chiller)

更新时间:2023-07-02 03:06:50 阅读: 评论:0

拉简隆多
AIR-COOLED Process CHILLERS SCROLL R407C, PACKAGED, with Tank PZAT18D-GE-Discovery-MR450
DISCLAIMER: Process chiller assignment for the GE Discovery MR450 application is bad on availab
le information at the time this document was generated. As with many industries, technical characteristics can change often. Plea contact Legacy Chiller Systems for capacity and feature verifications prior to ordering or specifying this equipment.
月饼
Legacy Chiller Systems, Inc.
Example: P Z A T 18 D E 5
P P = Packaged
IE = Indoor Evaporator
OC = Outdoor Condenr
Z Z = Scroll Compressor
S = Semi-Hermetic Compressor
A    A = Air-cooled Condenr
W = Water-cooled Condenr
T T = Integrated Stainless Steel Tank
PT = Integrated Poly Tank
N = Nexus Technology
18Nominal Capacity Tons
Ex.: 1.5 x 12,000 BTUH = 18,000 BTUH, etc.
D S = Single Compressor
D = Dual Compressor
E Electrical Requirement:
E = 208/230-1-60
F = 208/230-3-60
G = 460-1-60
H = 460-3-60
防溺水口诀I = 575-3-60
J = 220-1-50
K = 200/208-3-50
酒埠江风景区L = 380-3-50
5Refrigerant:
*4 = R134A
5 = R407C
嘉兴烟雨楼6 = R404A
* Special order refrigerant class
Legacy Chiller Model: PZAT18D
Industrial grade process chiller 6 to 15 tons Series
Standard Options
王者荣耀赏金赛Condenr fan cycle control (+40 ambient)
ETL listed
IDEC Pentra PLC control System with 5.7 inch ultra bright touch screen.
Copeland Scroll compressor(s)
STAINLESS STEEL brazed plate evaporator with insulation, and cured in a steel bracket STAINLESS STEEL storage tank with 1/2" insulation
潜心学习Fud STAINLESS STEEL re-circulation pump for tank operation with ball valve and cleanable strainer Compressor and hot gas valve time delays
24V control transformer
Suction accumulator
Water flow switch, Pump differential nsor
Hot gas by-pass capacity control
Direct drive condenr fan motor
Rust resistant, high CFM, aluminum condenr fan blade
Condenr(s): copper tube aluminum fin
Return fluid nsing thermostat
Liquid line drier, sight glass, solenoid, TEV
MICRO - High-pressure refrigerant control
MICRO- Low-pressure refrigerant control with time
MICRO - inlet and outlet realtime readouts.
Compressor motor contactor
新手怎样学理财
Painted galvanized steel sheet metal cabinet (30 tons and larger systems are GALVANIZED)
.5 in insulation on all water and refrigerant lines
Micro - Processor On - Off switch for control circuit operation
Micro - Processor automatic compressor lead lag on dual circuit units
Tank pressure relief valve, vent and drain connections
Full refrigerant charge from factory (407C) Standard
Computerized factory run testing under load conditions
Basic Technical Support
Standard LTL crating - Pallet, Foam vertical corners with platic wrap. Optional Enhanced Packaging is
available for most models.
Automatic condenr fan cycle control for air-cooled condenrs Five Year Extended Warranty Program
Factory offered options for this chiller model - Check mark indicates inclusion of this item
Auto city water changeover panel - Plea e (i) for sizing information
Auto city water changeover panel with filter - Plea e (i) for sizing information
Tank Low level auto city water make up
Tank low level indicator with dry contacts
E-Coat - Condenr Coil Coating (coastal protection)
Deduct - Plastic storage tank ction (Deduct available on lect chillers with internal tank systems) Process drop asmblies, one inch copper, wall mounted and ready to install
115 volt rvice outlet, rain-tight (Requires external ckt)
BACnet Gateway and Router, BB2-7030, IP to MS/TP, factory installed
Compressor fusing (230V)
Compressor fusing (460V)
Electrical system upgrade (575V 3ph 60HZ)
EWON - VPN access anywhere - Click (?) for more information
Fud disconnect (230V)
Fud disconnect (460V)
MOXA Five Port Unmanaged Network Switch - Factory Installed
Remote Chiller Controller Touchscreen - Shipped Loo
Voltage - pha monitor with touchscreen HMI indicator.
Factory REBATE - NEXUS Technology - Economizer System - Available Q1 2016 only
Legacy Integrated Economizer System - with NEXUS technology
Process water flow meter (20-100 gpm)
Process water flow meter (45-160 gpm)
Process water pressure gauge t in-out
Add-on package for Glycol applications
Evaporator heat tape freeze protection thermostatically controlled
Flooded condenr with HEATED receiver and head pressure control - 20F rating. For more information on this option - Click ?
Flooded condenr with receiver and head pressure control 0F rating. For more information on this option - Click ?
Casters (Factory mounted) for easy chiller re-location
Enhanced  LTL Crating - Pallet, hard wood slats enclosure and plastic wrap

本文发布于:2023-07-02 03:06:50,感谢您对本站的认可!

本文链接:https://www.wtabcd.cn/fanwen/fan/89/1063985.html

版权声明:本站内容均来自互联网,仅供演示用,请勿用于商业和其他非法用途。如果侵犯了您的权益请与我们联系,我们将在24小时内删除。

标签:溺水   风景区   赏金   潜心   理财   口诀
相关文章
留言与评论(共有 0 条评论)
   
验证码:
推荐文章
排行榜
Copyright ©2019-2022 Comsenz Inc.Powered by © 专利检索| 网站地图