戏曲的种类Note: Plea make sure to examine the following items before power-on:
* Reliable grounding of device enclosure.
* Power supply of the device is AC or DC and 240V.
(If 110V power supply is required, it shall be indicated during ordering.)
* Default of device input is passive contact input.
(If active contact input of DC 240V is required, it shall be indicated during ordering.)
* Default of the device is without anti-bouncer function新生儿喂奶姿势
(If product with anti-trip function is required, it shall be indicated during ordering.)
* Correct polarity of current input as well as correct pha quence of voltage input
* During on-site debugging, power-on time of high current shall not be too long (For this device, conti
nuous running is available when current in the AC current circuit is twice of the rated current, 10s running is allowable under ten times of the rated current and 1s running is allowable under 40 times of the rated current.), so as to avoid unnecessary damage.
1概述
YZ201/301系列综合微机保护装置是采用计算机技术、电力自动化技术、通信技术等多种高新技术的新型电器产品。它集保护、测量、控制、监测、通讯于一体,是实现电力系统自动化的基础硬件装置,是替代传统继电保护的理想电器元件,是构成智能化开关柜的理想电器元件。多种功能的高度集成、灵活的配置、完全汉化的显示技术、友好的人机界面,使得YZ201/301系列综合微机保护装置可做为电力系统10KV以下电网各类电器设备及线路的主保护或后备保护。对各种中压电网(不接地电网、电阻接地、消弧线圈接地、直接接地电网)均能适用。并且YZ201/301系列综合微机保护装置能应用在各类开关柜和各类接线方式的系统中,如单母线、双母线、旁路母线和双进线供电系统。
1. General
萎靡不振什么意思Taking various high and new technologies such as computer technology, electric power automation, communication technology, etc., and integrating protection, measurement, control, monitoring and communication into one, YZ201/301 ries integrated microcomputer protection device is a new type
of electric product, a basic hardware device to realize the automation of electric power system, as well as an ideal component to replace the traditional relay protection and to constitute the intelligent switch cabinet. A varieties of highly integrated functions, flexible tting, completely Chine-localized display technology and friendly human-computer interface enable the YZ201/301 ries integrated microcomputer protection device to be the main protection or back-up protection for various electric equipment and circuits with the grid below 10KV in the
electric power system. And YZ201/301 ries integrated microcomputer protection device
is not only applicable to all kinds of middle-voltage grids (ungrounded grids, resistance
grounding, arc suppression coil grounding and direct grounding grids), but to various
switch cabinets as well as systems of various connection ways such as single bus, double
bus, bypass bus and double inlet wire power supply system.
2  型号说明
针对保护设备及保护要求的不同,Y Z 201/301系列装置产品分类及用途如下表:Y Z201/301-C K
Y Z201/301-C X Y Z201/301-C B Y Z201/301-JX Y Z201/301-J X ZT Y Z201/301-J X ZF Y Z201/301-M F Y Z201/301-M FZT Y Z201/301-D D Y Z201/301-D R Y Z201/301-P T 型号
装置名称保护配置测控装置出线保护装置厂用变保护装置进线保护装置进线备自投装置进线自复装置母分保护装置母分备自投装置电动机保护装置
电容器保护装置PT监控装置控制回路断线告警,装置自检告警速断、限时速断、定时限过流、反时限过流、零序过流、三相一次重合闸、后加速跳、控制回路断线告警、
装置自检告警
速断、定时限过流、反时限过流、温度保护、瓦斯保
护、零序过流、控制回路断线告警、装置自检告警
速断、限时速断、定时限过流、反时限过流、低压保问候早安的句子
护、零序过流、控制回路断线、装置自检告警
速断、限时速断、定时限过流、反时限过流、进线备
自投、控制回路断线告警、装置自检告警
速断、限时速断、定时限过流、反时限过流、进线自
复、控制回路断线告警、装置自检告警
速断、限时速断、定时限过流、反时限过流、零序过
流、控制回路断线告警、装置自检告警
速断、限时速断、定时限过流、母分备自投、零序电
压告警、控制回路断线告警、装置自检告警
速断、反时限过流、零序过流、温度保护、低压保护、
控制回路断线告警、装置自检告警速断、定时限过流、零序过流、低压保护、过压保护、低周减载、PT断线告警、接地告警、控制回路断线告
警、装置自检告警
PT切换、PT 断线告警、接地故障告警、过压告警、
欠压告警、装置自检告警
注:Y Z201装置具有R S485通信功能,Y Z301没有通信功能,以下所涉及到的通                信功能均与Y Z
301无关。
2. Model Description
抚养费协议书范本Aiming at different protection equipment and protection requirements, the classification
Note: YZ201 device is equipped with RS485 communication function, but YZ301 is not, therefore the following communication functions have nothing to do with YZ301.
超级自控力3. Application Conditions
3.1 Working Environment
清理空间Altitude:      <3000m
Environmental Temperature:  -10℃ ~ +55 ℃
Relative Humidity: 50%RH ~ 95%RH
Atmospheric Pressure:  70kPa ~110kPa
3.2  环境要求
装置使用场所应无爆炸、无腐蚀气体及导电尘埃、无严重霉菌、无剧烈振动源,不允许有超过发电站范围内可能的电磁场存在。应有防御雨、雪、风、沙、尘埃及静电的措施。
3.2 Environmental Requirement
There shall be no explosive & corrosive gas, conductive dust, rious mildew and violent vibration source on the ground on working site of the device, and no possible electromagnetic field beyond the scope of the power plant is acceptable. Measurements to protect against rain, snow, wind, sand, dust and static  shall be provided.
3.3电源类型
交流 直流 额定电压
240V(-20%~+10%) 240V(-10%~+20%) 频率
50Hz (±5%) ——— 波形
正弦畸变<10% 波纹系数≤5% 功耗
<10W <10W苏轼词两首
3.3 Power Requirement 4  面板及操作
4.1 Front Panel Arrangement
4.1  前面板布置 Power Type
AC DC Rated Voltage
240V (-20%~+10%) 240V (-10%~+20%) Frequency
50Hz (±5%) ——— Waveform
Sine; distortion <10% Ripple factor ≤5% Power
Dissipation <10W <10W