缩写将相和6.2 03.2015•S u b j e c t t o m o d i fi c a t i o n
Damper actuator for adjusting air control dampers in ventilation and air-conditioning systems for building rvices installations • Torque 4Nm
• Nominal voltage AC/DC 24V • Control: Open-clo
(not made for 3-point applications)• Running time 2.5s
Electrical data
Nominal voltage
AC 24V, 50/60Hz / DC 24V
Nominal voltage range AC 28.8V / DC 28.8V Power consumption In operation At rest
For wire sizing
13W @ nominal torque 2W
23VA (I max. 20A @ 5ms)Connection
Cable 1m, 3 x 0.75mm ²
宠物种类
Functional data
Torque (nominal torque)Min. 4Nm @ nominal voltage
locked
Angle of rotation
Max. 95°, can be limited at both ends with adjustable mechanical end stops Angle of rotation limiting min. 30°Running time
2.5s / 90°
Automatic adjustment of
operating range to match the mechanical angle of rotation Manual triggering of the adaption by pressing the «Adaption» button
Sound power level 52dB(A)
Position indication Mechanical, pluggable
Negative torque
!
≤50% from nominal torque (with restrictions)*
Safety
Protection class III Safety extra-low voltage UL Class 2 Supply
Degree of protection IP54 in any mounting position NEMA 2, UL Enclosure Type 2EMC
东北人骂人CE according to 2004/108/EC
Certification
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 cULus according to UL 60730-1A and UL 6073
0-2-14 and CAN/CSA E60730-1:02Mode of operation Type 1Rated impul voltage 0.8kV Control pollution degree 3
Ambient temperature
–30...+40°C (no restrictions)!
+40...+50°C (with restrictions)*Non-operating temperature –40...+80°C
ping网关
Ambient humidity 95% r.H., non-condensating Maintenance
Maintenance-free Dimensions / Weight
Dimensions See «Dimensions» Weight
Approx. 0.97kg
Dimensional drawings杜甫号什么
Dimensions [mm]
* Option (accessory K-NA)
When using an auxiliary switch or feedback potentiometer.
Technical data
* Under the operating conditions, the lift cycle of actuator will be reduced. Plea contact your Belimo reprentative for details
150m
a t i o
n
Modulating damper actuator for adjusting air control dampers in ventilation and air-conditioning systems for building rvices installations • Torque 4Nm
• Nominal voltage AC/DC 24Vshirt
• Control: modulating DC (10V • Position feedback 10V • Running time 2.5s
Dimensional drawings
活塞航空发动机Dimensions [mm]
6.2 03.2015•S u b j e c t t o m o d i fi c a t i o n
Wiring diagrams: Open/Clo actuators – parallel connection possible, plea note the performance data Wiring diagrams: Modulating actuators – parallel connection possible, plea note the performa
nce data Wiring diagrams: Open/Clo actuators—parallel connection possible, plea note the performance data.
Wiring diagram: Modulating actuators—parallel connection possible, plea note the performance data.
Direction of rotation
Position - signal voltage