电气埋管施工工艺细那么甘蔗英语
Electrical conduit construction technology rules
1.严禁使用电焊、气焊割管。
Strictly prohibited in using gas and electric welding cutting conduit.
2.严禁将脚手架作为电缆管使用。
四神汤的做法
Strictly prohibited in using the folder as electrical conduit.
3.  锈蚀严重的钢管不得使用;钢管弯制或安装前应将管口与管杂物清扫干净,并除去毛刺。 
Exist rious corrosion conduit is not allowed ud;the mou of the conduit as the inner part the debris must be removed before bending or installation
3.电缆管切割采用手工锯或切割机进展切割,并保证切割面平整且不倾斜;切割后必须立即将管口毛刺打磨干净,并打磨管口成喇叭型。
Cutting for the conduit adoptingin manual saw or machine, and ensure the cutting surface smooth and not tilt;burring after cutting must be immediately, and polished type nozzle into horn.
4.电缆管的弯曲半径R≥10D〔电缆管外径〕;弯曲角度≥90°,并尽可能减少90°弯头;电缆管弯制不得出现明显的凹瘪、裂纹、折皱,钢管弯扁程度≤0.1D〔电缆管外径〕。
Bendingradius R ≥10D (here D is conduit out diameter);Bending Angle 90 °, and as less as possible the 90 °elbow; conduit bending cannot appear obvious concave, crack, wrinkle, flat steel tube bending flat level 0.1 D (here D is conduit out diameter).
6.电缆管安装时,每根电缆管弯头数量不得超过3个,90°弯头不得超过2个
〔埋管长度≥12米,不得多于2个弯头;12米≥埋管长度≥8米,不得多于3个弯头;直管埋设不得大于30米〕超过上述标准须增加转接盒。
When installation conduit, the amount of each conduit elbow shall not exceed 3, elbow with90 °shall not be more than 2;the conduit length 12m, shall not be more than two el
bow;
The length of the conduit that changed between 8m and 12m 职业考试, shall not be more than three elbow;
straight shall not be more than 30 meters
If exceedthe standard more than the standard must increa the transfer box.
7.电缆管连接不得对接焊,必须采用短套管套管长度≥50mm;
when conduit connection a short socketmust be ud,and no butt welding〔except spot welding〕;the lengthof the socket more than 2 times of conduit out diameter.
电缆管型号
Type
壁厚〔mm〕
Thickness
电缆管外径
〔mm〕
Out diameter.
连接套管径〔mm〕
Socketinner diameter
连接套管的长度〔mm〕
Length
DN25
3.25
33.5
35
≥50mm
DN32
3.25
42.3
43
≥50mm
DN50
3.5
60
61
≥50mm
DN80
4
88
89
≥50mm
8.电缆管连接时,先将套管中间凸台毛刺打磨干净,然后将电缆管插入套管中,电缆管与凸台之间不得留有间隙;连接套管与电缆管两侧均匀电焊4点,并用黑胶布缠绕封实;
When coupling, there shouldnt gap between the two conduit and the counterpart malocclusion is less than 2 mm, counterpart am should be in the middle of the socket, and the both sides along the circumferential welding aling, partialcannot welding must u black tape winding aling with fastened iron wire;
9.电缆管不得在外壁直接点焊加固,加固采用铁丝绑扎或煨制钢筋成环钩加固、切割20~30mm套管套至固定点进展,固定间距:φ15~φ20为1.0~1.5米,φ25~φ32为1.5~2.0米,φ40~φ50为2.0~2.5米,φ65以上不大于3米。
Pot welding reinforce cant be allowed outside the wall of conduit directly, a available steel bar will be made into a ring hook, and then cutting 20 ~ 30 mm one end fasten to conduit another one stable point or iron wire colligation
fixed spacing: φ15mm ~ 20mm is 1.0 ~ 1.0 m, from 25mm to 32mm is 1.5 ~ 1.5 meters, 40mm ~ 50mm is 2.0 ~ 2.5 meters, exceed 65mm not more than 3 meters
10.电缆管与接线盒的连接可采用焊接和丝扣连接,:电缆管伸入接线盒3~6mm
管口用黑胶布包扎结实,接线盒用湿棉纱、破布填实;外部用黑胶布缠绕,以防止水泥沙浆进入。
Welding and threaded can be ud for the connection between electrical conduit and sockets, electrical conduit are putted into the sockets 3 ~ 6 mm
The mou of the conduit with black adhesive bandage, internal parts of the socketfilled with a wet cotton yarn ,cloth;External with black tape winding, in order to prevent cement mortar having a access into.
11.接线盒安装时必须与模板紧贴,并用钢筋在接线盒四周加固;电缆管直径≤DN25的指明与消防报警预埋管放置于模板与钢筋网之间,预埋管绑扎在钢筋网上,与模板之间预留间隙≥15mm;电缆管在接线盒处的固定点与接线盒间距不得大于200mm。
Socket must be clingy to the template and reinforced around, between the electrical conduit and template rerved clearance 15 mm or more. into the sockets of the cable must be welding with a cross bar (from 6 or 8mm round steel;
12. 所有外露预留的电缆管与伸入分电箱、木制接线盒等管口应伸出砼面200mm以上,电缆管口必须封堵。续接收路用胶布封口后加套帽。
All thererved outside electrical conduit and tho into the distribution box, and wooden box should stretch out the concrete  over 200mm,adding iron plate welding al, steel plate with cutting machine and smooth.The continued jacketed pipe t a cover after aling with tape.
13.电缆管过缝制作:采用在电缆管外比电缆管外径大两级套管,套管与电缆管口部密实封堵,电缆管套管制作规格,长度如下:
Manufacture for expansion joint, adopting the two levels of casing pipe coat than electrical conduit diameter, first winding linen between casing and electrical conduitthen filling with asphalt clo-grained,
Specifications, the length is as follows:
明星人体摄影
电缆管型号
Type
壁厚〔mm〕
thickness
电缆管外径〔mm〕out diameter
过缝套管规格
specification
过缝套管径〔mm〕
Inner diameter
过缝套管的长度〔mm〕length
φ25
郑州旅游景点推荐3.25
33.5
φ40
41
600
φ32安亭是上海哪个区
3.25
42.3
φ50
猪骨高汤53
800
φ50
3.5
60
φ80
80.5
1200
φ80
4
88.5
φ125
131
1800
社区个人工作总结
14. 同一处电缆管超过3根,出砼必须排列整齐、美观〔横平竖直 〕;图纸没有明确要求时,按下述原那么排列:〔1〕:电缆管由大到小顺序排列;〔2〕:3~9根可排列成一排或两排;〔3〕:10根与以上必须排列成两排或两排以上,且每排宽度大致相当,宽度相差宜小于两根埋管的直径;〔4〕成排电缆管预留高度〔或长度〕一致。