CABLE ACCESSORIES
PG-CA-0506
For 5kV-35kV Distribution Systems
Loadbreak & Deadbreak Separable Connectors
Cable Joints
Cable Termination
Surge Arresters
Fud Elbows Product Selection Guide
PG-CA-0506 Page 4
200 Amp loadbreak connectors and accessories provide a convenient method to connect/disconnect
cable and equipment on power distribution systems. Loadbreak elbows include provisions for energized operation using standard hotstick tools, allowing load-make/break operation and a visible
颐和园图片
disconnect. Components can be isolated with insulated caps, plugs and parking bushings.
Optional accessories allow system grounding, testing, bypass, lightning surge protection and current limiting fusing. Additional connecting points and taps can be provided by u of junctions or feed-thrus.
PG-CA-0506 Page 5
N1.Copper lug for u on COPPER CONDUCTOR ONLY.
N2.W5X indicates that the part number includes 02500X long bi-metal compression
lug as standard. For an all-copper lug, replace W5X with W2X in Table X1 to specify the all-copper 0
公鸡进行曲2702X lug.
N3.Also available as housing only. Specify: 165BLR-W; 275BLR-W;
375BLR-W; 166BLR-W; 276BLR-W; 376BLR-W.
N4.Also available as elbow/inrt combination. Specify: 165A4-WX;
275A4-WX; 166A4-WX; 276A4-WX.
N5.Also available with 200ECS jacket al included. Add - “S” suffix to part number.N6.Rated for single-pha applications only.N7.Equipped with insulated cuff.
明天拼音
N8.Includes internal torquing feature using 200AT Asmbly Tool.
N9.Also available without probe. Specify “A” suffix - Example: 273DRGA.
N10.Repair elbow has extended length contact and elbow housing resulting in a net
gain of 3-1/4" in length.
N11.Replacement elbow has extended length contact and elbow housing resulting
in a net gain of 8-7/8" in length.
N12.Rated for 25kV thru 35kV applications.N13.Includes long bi-metal contact 00400X.
N14.160CA Cable Size Adapter can only be ud with elbow part numbers
165LR/166LR C size only.
N15.See page 6 for WX size tables and for fu sizes.
N16.Fully rotatable for 360°positioning. Includes bail asmbly to cure feed-thru
inrt to bushing well.
N17.Includes 02800X bi-metal contact.
N18.Includes 02509X long bi-metal contact.
N19.Includes built-in jacket al. Also available as housing only — specify:冒菜怎么做
165BLRJS-W, 166BLRJS-W, 275BLRJS-W or 276LRJS-W. Also available as elbow/inrt combination — specify: 165JSA4-W5X, 166JSA4-W5X,275JSA4-W5X or 276JSA4-W5X.
N20.Includes a yellow ating indicator and vent ring.N21.Includes a black vent ring.
Refer to the W and X tables on pages 34 and 35 for sizing to cable insulation diameter and conductor size.
For cable shield adapters and jacket als, e page 30.
CONTACTS, PROBES, PLUGS, CABLE ADAPTERS AND JUNCTIONS CONTINUED ON PAGE 7.
PG-CA-0506 Page 10
600 Series deadbreak elbows, straight recepta-cles, junctions, vault stretchers and accessories are ud to connect equipment and cable on primary feeder and network circuits. Designs accommodate large conductors and feature bolted connections and deadfront modular
construction for maximum reliability, perfor-mance and versatility.
DE-ENERGIZED connectors can be quickly and easily connected and disconnected using standard hand tools and equipment in accordance with accepted operating practices. Optional accessories allow visible external paration, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arresters and circuit protection.
Hot-stick operable and parable joint systems are shown on pages 14 thru 19.
PG-CA-0506 Page 11
N1. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656; K671
for K651; K675 for K650 and K655; K676 for K656; 775 for 750 and 755;776 for 756 and 2X for 0X in the part number. The 900 Amp rating requires copper current-carrying connector components and copper conductor cable.
N2. Add suffix symbol from page 31 to include cable shield grounding kit
and/or cable jacket aling kit.
N3. Available without the stud by adding “N” to the part number.
N4. Straight Receptacle Adapter is ud to connect Straight Receptacles
K655YBSR and K655YSR-W0X (Pg.14) to equipment bushings.N5. Aluminum lug for u on aluminum or copper conductors. DO NOT
国外广告substitute threaded 03600X lug.
N6. Copper lug for u on COPPER CONDUCTOR ONLY. DO NOT substitute
threaded 03602X lug.
hdmi音频
N7. Available with the stud factory-asmbled by adding “SP” to the part
number. 675ETP , K675ETP and 775ETP are available as -SP only. The stud is not field removable.
N8. Available with a loo stud by adding suffix “S” to the part number.N9. 600SW spanner wrench is recommended for installation of K650CP
生理期减肥
connecting plug, deadbreak reducing tap plugs and reducing tap wells.N10. U 600ATM Asmbly Tool.房屋出售范文
N11. Rubber junction with stainless steel mounting plate and back plate.
Add “-U” for rubber junction with stainless steel mounting plate, back plate and adjustable mounting bracket.Add “-4” for rubber junction only.
Add “-5” for rubber junction, stainless steel U-straps and back plate.N12. 600 Series Elbows and Straight Receptacles with IEEE Std. 386
capacitive test points are available by substituting 656 for 655; K656 for K655; K676 for K675; 756 for 755; 676 for 675; K676 for K675 and 776for 775 in the part number.
N13. See page 17 for Window-Op Connector Kit.N14. Superded by K651CP .
N15. Two - six-position multi-point junctions shown on pages 20 and 21.
Refer to the W and X tables on pages 34 and 35 for sizing to cable insulation diameter and conductor size.
For cable shield adapters and jacket als, e page 30.