SETUP AND OPERATING
INSTRUCTIONS
Mark II
Diel Engine Fire Pump Controllers
业余赚钱
不知不觉近义词
开国大典课件
IMPORTANT - DO NOT DISCARD
NS1100-40
Clo
Print E-Mail
Table of Contents
SECTION ONE Introduction (1)
Mounting Legs (1)
Mounting Controller (1)
Wall Mount (1)
Floor/Ba Plate Mount (2)
Making Electrical Connections (3)
Making Pressure Connections (3)
SECTION TWO
Mark II Setup Notes (5)
Mark II Menu Structure - Overview (6)
Mark II Menu Structure - Meter Menu (7)
Event Log Menu (8)
Data Log Menu (9)
Print Menu (10)
Pressure Settings Menu (11)
Timers Menu (12)
Clock Set Menu (13)
Diagnostics Menu (14)
System Setup Menu (15)
i
Table of Contents
Detailed Instructions
Meter Function (16)
Event Log (17)
Data Log (18)
Print Menu (if printer installed) (19)
Pressure Settings
Start Pressure (20)
Stop Pressure (21)
Pressure Recording (22)
Manual Stop Only (23)
Pressure Units (24)
Low Suction & Level (25)
Pressure Calibration (26)
Timers
On Delay Time (27)
Minimum Run Time (28)
天秤座幸运数字Off Delay Time (29)
Weekly Test Time (30)
AC Power Loss Start Delay Time (31)
Clock Set (32)
Daylight Savings Time (33)
Diagnostics
Software Version (34)
Lamp Test (35)
Discrete Inputs (1-16) (36)
Discrete Inputs (17-32) (37)
ii
Table of Contents
烟的拼音
Diagnostics (cont..)
Discrete Outputs (1-12) (38)
Discrete Outputs (13-24) (39)
System Setup
Change Passwords (40)
Save To Disk Function (41)
油麦菜怎么吃Information Supplied Separately in Controller Information Packet
Publication GF100-01 - Sales and Service Office Directory
Controller Drawings
iii
INTRODUCTION
Firetrol® FTA1100 combined automatic and manual diel engine fire pump controllers are intended for starting and monitoring fire pump diel engines. They are available for u with 12 or 24 volt negative ground systems using lead acid or Nickel-Cadmium batteries. FTA1100 fire pump controllers are listed by Underwriters Laboratories Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment (cUL), and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code.
The instructions are intended to assist in the understanding of the installation and operation of the FTA1100. Read through the instructions thoroughly prior to connecting the controller. If there are any questions unanswered in the instructions, plea contact the local Firetrol reprentative or factory rvice department.
MOUNTING LEGS (OPTIONAL)
Procedure—
1.If legs were supplied, unpack legs and mounting hardware.
2.Inspect legs for damage.
3.Place shipping carton tube on floor and gently lay the controller, on its back, on top of tube.
4.Attach each leg to the bottom of the enclosure using the 3 nuts, and washers provided for
each leg . Tighten nuts curely.
5.After legs are curely attached, stand the controller up on its legs for floor mounting. Each
我的家leg has 3 holes on the bottom for anchoring to the floor or ba plate.
水瓶座性格特点
Caution—Controller is not free standing! Controller must be cured to floor or wall surface before opening door or operating.
MOUNTING CONTROLLER—
Note—Consult the appropriate job plans to determine controller mounting location. Controller must be mounted within 20 feet of the engine.
Tools and Materials (all mounting):
1.Assortment of common hand tools of the type ud to rvice electromechanical equip-
ment.
2.Drill for drilling wall/floor anchor holes.
3.Hand level.
4.Tape measure.
5.Four (4) anchors with bolts and washer—if wall mount. Six (6) anchors, bolts and washers—
if floor/ba mount.
Wall Mount—
Note—Refer to the controller dimension drawing, DD1100, included in the instruction manual for necessary mounting dimensions.
The controller is wall mounted by using four (4) wall anchors, 2 anchors for the top ears and 2 anchors for the bottom mounting slots. The ears and slots are dimensionally on the same center-line for ea in mounting.
1.Using either the dimension print or by measuring the distance between the center lines of
the 2 lower slots, transcribe this dimension onto the wall. Note: The bottom edge of the enclosure should be a minimum of 12" (305 mm.) from the floor in ca flooding of the pump room occurs.
1