1 Power Quality Monitoring
Patrick Coleman
birdie
Many power quality problems are caud by inadequate wiring or improper grounding. The problems can be detected by simple examination of the wiring and grounding systems. Another large population of power quality problems can be solved by spotchecks of voltage, current, or harmonics using hand held meters. Some problems, however, are intermittent and require longer-term monitoring for solution.
Long-term power quality monitoring is largely a problem of data management. If an RMS value of voltage and current is recorded each electrical cycle, for a three-pha system, about 6 gigabytes of data will be produced each day. Some equipment is disrupted by changes in the voltage waveshape that may not affect the rms value of the waveform. Recording the voltage and current waveforms will result in about 132 gigabytes of data per day. While modern data storage technologies may make it feasible to record every electrical cycle, the task of detecting power quality problems within this mass of data is daunting indeed.
Most commercially available power quality monitoring equipment attempts to reduce the recorded data to manageable levels. Each manufacturer has a generally proprietary data reduction algorithm. It is criti
cal that the ur understand the algorithm ud in order to properly interpret the results.
smn是什么意思
1.1Selecting a Monitoring Point
immobilePower quality monitoring is usually done to either solve an existing power quality problem, or to determine the electrical environment prior to installing new nsitive equipment. For new equipment, it is easy to argue that the monitoring equipment should be installed at the point nearest the point of connection of the new equipment. For power quality problems affecting existing equipment, there is frequently pressure to determine it. the problem is being caud by some external source, i. e., the utility. This leads to the installation of monitoring equipment at the rvice point to try to detect the source of the problem. This is usually not the optimum location for monitoring equipment. Most studies suggest that 80% of power quality problems originate within the facility. A monitor installed on the equipment being affected will detect problems
originating within the facility, as well as problems originating on the utility. Each type of event has distinguishing characteristics to assist the engineer in correctly identifying the source of the disturbance.
1.1.1 What to Monitor
challengerAt minimum, the input voltage to the affected equipment should be monitored. If the equipment is single pha, the monitored voltage should include at least the line-to~neutral voltage and the neutral to-ground voltages. If possible, the Iine_to_ground voltage should also be monitored. For three-pha equipment, the voltages may either be monitored line to neutral, or line to line. Line-to-neutral voltages are easier to understand, but most three-pha equipment operates on line-to-line voltages. Usually, it is preferable to monitor the voltage line to line for three-pha equipment.
If the monitoring equipment has voltage thresholds which can be adjusted, the thresholds should be t to match the nsitive equipment voltage requirements. If the requirements are not known, a good starting point is usually the nominal equipment voltage plus or minus 10%.
In most nsitive equipment, the connection to the source is a rectifier, and the critical voltages are DC. In some cas, it may be necessary to monitor the critical DC voltages. Some commercial power quality monitors are capable of monitoring AC and DC simultaneously, while others are AC only.
It is frequently uful to monitor current as well as voltage. For example, if the problem is being caud by voltage sags, the reaction of the current during the sag can help determine the source of t
he sag. If the current doubles when the voltage sags 10%, then the cau of the sag is on the load side of the current monitor point. If the current increas or decreas 10 - 20% during a 10% voltage sag, then the cau of the sag is on the source side of the current monitoring point.
drilldown
Sensitive equipment can also be affected by other environmental factors such as temperature, humidity, static, harmonics, magnetic fields, radio frequency interference (RFl), and operator error or sabotage. Some commercial monitors can record some of the factors, but it may be necessary to install more than one monitor to cover every possible source of disturbance.
It can also be uful to record power quantity data while arching
for power quality problems. For example, the author found a shortcut to the source of a disturbance affecting a wide area by using the power quantity data. The recordings revealed an increa in demand of 2500 KW immediately after the disturbance. Asking a few questions quickly led to a nearby plant with a 2500 KW switched load that was found to be malfunctioning.linebreak
1.2Selecting a Monitor
haarp
Commercially available monitors fall into two basic categories: line disturbance analyzers and voltag
e recorders. The line between the categories is becoming blurred as new models are developed. Voltage recorders are primarily designed to record voltage and current strip chart data, but some models are able to capture waveforms under certain circumstances. Line disturbance analyzers are designed to capture voltage events that may affect nsitive equipment. Generally, line disturbance analyzers are not good voltage recorders, but newer models are better than previous designs at recording voltage strip charts.
In order to lect the best monitor for the job, it is necessary to have an idea of the type of disturbance to be recorded, and an idea of the operating characteristics of the available disturbance analyzers. For example, a common power quality problem is nuisance tripping of variable speed drives. Variable speed drives may trip due to the waveform disturbance created by power factor correction capacitor switching, or due to high or low steady state voltage, or, in some cas, due to excessive voltage imbalance. If the drive trips due to high voltage or waveform disturbances, the drive diagnostics will usually indicate an over voltage code as the cau of the trip. If the voltage is not balanced, the drive will draw significantly unbalanced currents. The current imbalance may reach a level that caus the drive to trip for input over current. Selecting a monitor for variable speed drive tripping can be a challenge. Most line disturbance analyzers can easily capture the waveshape distu
rbance of capacitor switching, but they are not good voltage recorders, and may not do a good job of reporting high steady state voltage. Many line disturbance analyzers cannot capture voltage unbalance at all, nor will they respond to current events unless there is a corresponding voltage event. Most voltage and current recorders can easily capture the high steady state voltage that leads to a drive trip, but they may not
capture the capacitor switching waveshape disturbance. Many voltage recorders can capture voltage imbalance, current imbalance, and some of them will trigger a capture of voltage and current during a current event, such as the drive tripping off.
To lect the best monitor for the job, it is necessary to understand the characteristics of the available monitors. The following ctions will discuss the various types of data that may be needed for a power quality investigation, and the characteristics of some commercially available monitors.
I. 3 Voltage
The most commonly recorded parameter in power quality investigations is the RMS voltage delivered to the equipment. Manufacturers of recording equipment u a variety of techniques to reduce the volume of the data recorded. The most common method of data reduction is to record Mi
n/Max/Average data over some interval. Figure I. I shows a strip chart of rms voltages recorded on a eyeIe-by-cycle basis. Figure I. 2 shows a Min/Max/Average chart for the same time period. A common recording period is I week. Typical recorders will u a recording interval of 2 - 5 minutes. Each recording interval will produce three numbers: the rms voltage of the highest I cycle, the lowest I cycle, and the average of every cycle during the interval. This is a simple, easily understood recording method, and it is easily implemented by the manufacturer. There are veral drawbacks to this method. If there are veral events during a recording interval, only the event with the largest deviation is recorded. Unless the recorder records the event in some other manner, there is no time~stamp associated with the events, and no duration available. The most critical deficiency is the lack of a voltage profile during the event. The voltage profile provides significant clues to the source of the event. For example, if the event is a voltage sag, the minimum voltage may be the same for an event caud by a distant fault on the utility system, and for a nearby large motor start. For the distant fault, however, the voltage will sag nearly instantaneously, stay at a fairly constant level for 3-10 cycles, and almost instantly recover to full voltage, or possibly a slightly higher voltage it. the faulted ction of the utility system is parated. For a nearby motor start, the voltage will drop nearly instantaneousIy,
and almost immediately begin a gradual recovery over 30 - 180 cycles to
a voltage somewhat lower than before. Figure 1.3 shows a cycle-by-cycle recording of a simulated adjacent feeder fault, followed by a simulation of a voltage sag caud by a large motor start. Figure I.4 shows a Min/Max/Average recording of the same two events. The events look quite similar when captured by the Min/Max/Average recorder, while the cycle-by-cycle recorder reveals the difference in the voltage recovery profile.
FIGURE 1.1 RMS voltage strip chart, taken cycle by cycle.
FIGURE I. 2 Min/Max/Average strip chart, showing the minimum single cycle voltage, the maximum single cycle voltage, and the average of every cycle in a recording interval. Compare to the Fig. I. I strip chart data.fighting 什么意思