75-07023-000-F D9124 Spec Sheetdoc

更新时间:2023-05-25 22:07:27 阅读: 评论:0

D9124                                                    Addressable Fire Alarm Control Panel
Features
•127 addressable point system expandable to 246 address
•  2 supervid onboard Notification Appliance Circuits (NACs) with individual circuit silencing •Supports up to 128 off board relay outputs with programmable alarm output options
美术艺考培训机构•24 V DC power for Sensor and Notification Alarm Circuits
•12 V DC, 1.4 A power for accessory devices
•16-character Fire System Controller with custom English text annunciation
•Up to 8 supervid or 32 unsupervid remote Fire Annunciators
•Fire Test Mode
•500 event activity Logger
•Skeds rvice reminder for local systems
•Low Battery, AC power supply, and Battery lead supervision
•Dual phone line monitor
•Complete event reporting to receiver •Programming modem for remote diagnostics •Suitable for ADA applications
•Meets NFPA 72 National Fire Alarm Code
Standards
D escription
T he D9124 Alarm Panel is a 127-point addressable system that is expandable to 246 addressable points. The panel is programmable for fire, fire supervisory, or intrusion applications, directly through the controller, or remotely over telephone lines.
T he panel receives information from alarm initiating points through integrated devices over a two-wire multiplex zone expansion system (zonex).  It reports events through custom text displays on the controllers and annunciators.  Each addressable point accommodates normally open and/or normall
y clod devices with End-Of-Line resistor supervision  Events can be reported locally or communicated to a central station by a built-in digital communicator.
S ystem Notification Appliance capacity may be extended beyond the two supervid circuits by adding D8129 OctoRelay Modules.  Up to 128 relay outputs can be operated through the Controller, through the central station, or programmed for automatic operations.
gloomyN otification Appliances may be programmed for steady, puld, California Uniform Fire Code, March Time, or Temporal Code 3 patterns.  Temporal Code 3 patterns may be synchronized using the D411/D412 Synchronization Modules.
有志者事竟成
T wo fire system controllers and one fire system annunciator are available as options.  A fire system controller is visible and accessible behind a  locked, clear sliding panel located on the enclosure door.  It displays programmable text identifying specific initiating and supervisory devices and provides point annunciation as well as signal silence, trouble silence, detector ret, and annunciator ret.  The sliding panel lock is keyed to match the Radionics manual stations for retting the system.
T he 4 A, 24 V power supply charges the standby bat-teries and powers auxiliary devices.  It also supervis all of its critical circuits.  The power supply responds to low battery or battery disconnect conditions with a Trouble LED and a Trouble Relay for to sounders or lights.
F ive system power trouble conditions are lected by dip switches.  They can be individually identified to a central station, or grouped to activate a trouble relay, allowing a single supervid address to monitor the power supply.
A pair of 12 V batteries provide standby power.  Two additional batteries provide standby power for initiating and notification devices.  All four batteries are houd within the panel enclosure.  Batteries are not included in the D9124 and must be purchad parately.
T he D9124’s memory Logger stores 500 events including time, date, point and ur ID for each event. Programming options allow restriction of specific event reports to the central station receiver.  A programming option allows the Logger to record certain functions entered at command centers
T he 500 events in memory may be displayed at the fire system controller(s) or may be retrieved with a single
© 2001 Radionics, a division of Detection Systems, Inc. PO Box 80012, Salinas, CA 93912-0012, USA (800) 538-580775-07023-000-F12/01
D9124
Page 2 of 2
phone call by a central station using the Radionics
D5300 Remote Account Manager software package.
T he D5300 remote programming software allows the following to be controlled from a central station:•ret of notification appliances,
•activation/deactivation of remote annunciation,•relays,
•interrogation of battery,
•point and armed status,
•enabling or disabling of reporting functions,•shunting of reporting points during rvicing.
船务英语O ptions
T he alarm verification feature reduces the possibility
of fal alarm by requiring a ret and a cond alarm signal from the device before the panel rais an整数集
alarm condition.
T he optional Radionics D6500 Receiver and Radionics Modem II reporting format provide individual
point reporting to monitoring facilities.
T he D9131A Printer Interface Module allows an on-
site parallel printer to print events as they are stored in the Logger, recording time, date, account number, event, point ID, point text, and if the message has been transmitted to a receiver.
A pplication
T he D9124 controls complex alarm systems ud in schools, universities, manufacturing plants, and health care facilities. It has keyed controller access and is suitable for installation in public access areas.
I nstallation
T he D9124 is a modular asmbly, installed in a red 16-gauge steel enclosure, which can be surface- or flush-mounted.
S pecifications
D9124
P rimary power120 V AC Primary  (60 Hz, 360 VA)
O perating Current C ontrol: 462 mA Idle, 874 mA Alarm
+ nsor load
A ux. Power Supply24 V DC nominal @ 1.8 amps
N otification Appliance Circuits (NAC)
(Output)
2 On-board Circuits, 1.8 amp per circuit max.
naeti
T otal Current (Combined with 24 V Aux. Power) =
peer是什么意思
4 A. 560 O, 2 W EOL Resistor
a bite of china
O ff-board Relays U p to 16 Optional D8129 Form “C” Relay Modules
(8 Relay Outputs per Module)
S ensor Technology2-wire addressable circuit
S ensor Circuits U p to two 8125 POPEX (Point of Protection
Expander) Modules
Sensor Device
Address per POPEX119
T otal System Address 246
S ensor Circuit
Protection
P ower limited to 4 A
S hort circuit, rever polarity, thermal overload and
current overload protection on-board
D isplay16-character alphanumeric vacuum fluorescent
display
K eyboard8-key Function and Navigation Keys
R emote Annunciator*
(Optional)新年好英文
16-Character Remote Vacuum Fluorescent Display
Remote Annunciators
R emote Controller*
(Optional)
16-Character 8-key Remote Vacuum Fluorescent
Display Controllers
P rinter O ptional (Parallel)
O perating
Temperature
32° F - 122° F @ 85% Relative Humidity, Non-
condensing
* Up to 8 Supervid or 32 Unsupervid Annunciators and/or Controllers
D imensions
E nclosure Dimensions Removable Door:
Width:22-1/8”Width:23-5/16”
H eight: 36-1/16”Height: 37-1/16”
D epth: 3-1/16”Depth: 1-1/16”
L istings and Approvals
•Underwriters Laboratories
•California State Fire Marshal: 07165-0801:112
•NYC-MEA
•Factory Mutual
Ordering Information
No.Description Qty.
D9124Basic System, Includes  (1)
D9101Enclosure Asmbly with Door  (1)
D9100Accessory Module Carrier, Inc.  (1)
D192C Indicating Circuit Supervision Module
(2)
D928Dual Phone Line Switcher  (1)
D1256Fire Command Center  (1)
D9142LC24 V DC Power Supply  (1)
D8125Point of Protection Expander(1) (1*)
D1601Transformer  (1)
D9112LTB Control/Communicator Panel  (1)
Optional as required by expanded system
D1255R Security/Fire Command Center (a/r)
D1256R Fire Command Center (a/r)
D1257Remote Fire Alarm Annunciator (a/r)
D125B Dual Class B Style A Initiating Module
(D138 required) (a/r)
D129Dual Style D Initiating Circuit Module
(D138 required) (a/r)
D8125Point of Protection EXpander (POPEX)
(D138 required) (a/r)
D8127Point of Protection Transponder (D138
required)
(a/r)
D8129OctoRelay Module (D138 req’d) (a/r)
D8130Relea Module (D138 req’d) (a/r)
D9131Printer/Parallel Printer Interface Module
2199什么意思
(a/r)
D138Accessory Mounting Bracket (a/r)
D5200CE Hand Held  Programmer  (*)
D12612V, 7Ah Battery (a/r)
D121812V, 17.2 Ah Battery (a/r)
a/r:  as required by the system design  * additional optional

本文发布于:2023-05-25 22:07:27,感谢您对本站的认可!

本文链接:https://www.wtabcd.cn/fanwen/fan/78/776013.html

版权声明:本站内容均来自互联网,仅供演示用,请勿用于商业和其他非法用途。如果侵犯了您的权益请与我们联系,我们将在24小时内删除。

标签:艺考   美术   机构   培训
相关文章
留言与评论(共有 0 条评论)
   
验证码:
推荐文章
排行榜
Copyright ©2019-2022 Comsenz Inc.Powered by © 专利检索| 网站地图